Precautions Concerning Programs
4-24
Example 2: External output of the elapsed value in a timer number specified
by a digital switch
1
Programmable
controller
WX1
7-segment
indicator
WY3
R1
DF F81 BIN, WX1, IX
1
2
F80 BCD, IXEV0, WY3
Timer elapsed
value display
Digital
switches
Timer
number
setting
1
Convert the BCD timer number data in WX1 to binary, and
set it in index register IX.
2
Convert the elapsed value data EV in the timer specified
by IX to BCD, and output it to word external output relay
WY3.