5-28
5.1.4 Table of System Registers for FP-e
FP-e
No. Name
Default
value
Descriptions
5
Starting number setting for
counter
100
0 to 144
6
Hold type area starting
number setting for timer and
counter
140 0 to 144
7
Hold type area starting
number setting for internal
relays
61 0 to 63
8
Hold type area starting
number setting for data
registers
1652 0 to 1660
Hold/
Non-
hold
14
Hold or non-hold setting for
step ladder process
Non-hold Hold/Non-hold
(See note.)
20
Disable or enable setting for
duplicated output
Yes
FPWIN GR:
Disabled
Fixed
FPWIN GR: Disabled/Enabled
26
Operation setting when an
operation error occurs
Stop Stop/Continuation of operation
Dis-
abled:
When a battery error occurs,
a self-diagnostic error is not
issued and the ERROR LED
does not light.
Action
on
error
4
Alarm battery error
(Operating setting when
battery error occurs)
Disabled
Ena-
bled:
When a battery error occurs,
a self-diagnostic error is
issued and the ERROR LED
lights.
31
Wait time setting for multi-
frame communication
6500.0 ms 10 to 81900 ms
Time
set-
ting
34
Constant value settings for
scan time
0.0 ms
0: Normal scan
0 to 160 ms: Scans once each
specified time interval
Note) Use models without a Real-Time Clock(Clock/Calendar) function with the default value left as is.
If you change the setting the hold/non-hold operation will be unstalbe.
Settings are valid for models with a Real-Time Clock(Clock/Calendar) time function.