5-116
FP-X
Item
Add-
ress
Name
Default
value
Description
410 Unit No. setting 1 1 to 99
Communication
mode setting
Computer link
Computer link
General-purpose serial communication
PC(PLC) link
MODBUS RTU
412
Selection of modem
connection
Disabled Enabled/Disabled
413
Communication
format setting
Data length
bit: 8 bits
Parity check:
Odd
Stop bit: 1 bit
Enter the settings for the various items.
- Data length bit: 7 bits/8 bits
- Parity check: none/with odd/with even
- Stop bit: 1 bit/2 bits
- The following setting is valid only when
the communication mode specified by
system register 412 has been set to
“General-purpose serial communication”.
- Terminator: CR/CR+LF/None
- Header: STX not exist/STX exist
415 Baud rate setting 9600 bps
2400 bps
4800 bps
9600 bps
19200 bps
38400 bps
57600 bps
115200 bps
416
Starting address for
received buffer of
general (serial data)
communication mode
0 0 to 32764
COM.
1
port
set-
ting
417
Buffer capacity
setting for data
received of general
(serial data)
communication mode
2048 0 to 2048
Note1) The communication format in a PC(PLC) link is fixed at the following settings:
Data length is 8 bits, odd parity, stop bit is 1.
The communication speed (baud rate) is fixed at 115200 bps.
Note2)
Reference: For information on MODBUS RTU mode operation, <MODBUS RUT
Specifications>.