5-154
For the FP2SH/FP10SH, the index registers can be set to hold type or non-hold type. The register
numbers and settings are related as shown below.
Bank number Set value for I0 to ID Bank number Set value for I0 to ID
Bank 0 0 to 13 Bank 8 112 to 125
Bank 1 14 to 27 Bank 9 126 to 139
Bank 2 28 to 41 Bank A 140 to 153
Bank 3 42 to 45 Bank B 154 to 167
Bank 4 56 to 69 Bank C 168 to 181
Bank 5 70 to 83 Bank D 182 to 195
Bank 6 84 to 97 Bank E 196 to 209
Bank 7 98 to 111 Bank F 210 to 223
Default value of hold type area setting
Type
Area
FP2 FP2SH
Timer All non-hold type
Counter All hold type
Non-hold type: 200 words
(WR0 to WR199)
Non-hold type: 500 words
(WR0 to WR499)
Internal relay
Hold type: 53 words
(WR200 to WR252)
Hold type: 387 words
(WR500 to WR886)
Data register All hold type
File register All hold type
Link relay for MEWNET-W All hold type
Link register for MEWNET-W All hold type
Index register - All hold type
Type
Area
FP10SH
Timer All non-hold type
Counter All hold type
Non-hold type: 500 words (WR0 to WR499)
Internal relay
Hold type: 387 words (WR500 to WR886)
Data register All hold type
File register All hold type
Link relay for MEWNET-W/P All hold type
Link register for MEWNET-W/P All hold type
Link relay for MEWNET-H All hold type
Link register for MEWNET-H All hold type
Index register for FP10SH All hold type