5-202
Name Boolean Symbol Description
Steps *5 *6
FP-e
FP0
FP0R
FPΣ
FP-X
FP2
FP2SH/FP10SH
Push stack PSHS
Stores the operated result up to this
instruction. *2
1
Read stack RDS
Reads the operated result stored by the
PSHS instruction. *2
1
Pop stack
POPS
Reads and clears the operated result
stored by the PSHS instruction
1
Leading edge
differential
DF
Turns on the contact for only one scan
when the leading edge of the trigger is
detected.
1
Trailing edge
differential
DF/
Turns on the contact for only one scan
when the trailing edge of the trigger is
detected.
1
Leading edge
differ-ential
(initial execution
type)
DFI
Turns on the contact for only one scan
when the leading edge of the trigger is
detected. The leading edge detection is
possible on the first scan.
1
Set
SET
Output is set to and held at on.
3
Reset
RST
Output is set to and held at off.
3
Keep KP
Outputs at set trigger and holds until
reset trigger turns on.
1
(2)
No operation NOP
No operation.
1
Basic function instructions
TML
After set value “n” x 0.001 seconds,
timer contact “a” is set to on.
3
(4)
*3
TMR
After set value “n” x 0.01 seconds, timer
contact “a” is set to on.
3
(4)
*3
TMX
After set value “n” x 0.1 seconds, timer
contact “a” is set to on.
3
(4)
*3
On-delay timer
TMY
After set value “n” x 1 second, timer
contact “a” is set to on.
4
(5)
*3
Auxiliary timer
(16-bit)
F137
(STMR)
After set value “S” x 0.01 seconds, the
specified output and R900D are set to
on.
5
Auxiliary timer
(32-bit)
F183
(DSTM)
After set value “S” x 0.01 seconds, the
specified output and R900D are set to
on.
7
Time constant
processing
F182
Executes the filter processing for the
specified input.
9
*4
*4
Counter
CT
Decrements from the preset value “n”
3
(4)
*3 *3
*3
: Available, : Not available, : Not available partially
*1) The type of the devices that can be specified depends on the models.
*2) The allowable number of using the PSHS and RDS instruction depends on the models.
*3) For FP2SH, FP10SH and FP-X Ver2.0 or later, any device can be set for the setting value of counter or timer instruction.
*4) This instruction is available for FP-X Ver. 2.0 or later.
*5) In the FP2/FP2SH/FP10SH, when using Y1280, R1120 (special internal relay included), L1280 or anything beyond for the
KP instruction, the number of steps is shown in parentheses. Also, in the FP2/FP2SH/FP10SH, when a relay number has
an index modifier, the number of steps is shown in parentheses.
*6) In the FP2/FP2SH/FP10SH, when timer 256 or higher, or counter 255 or lower, is used, the number of steps is the number
in parentheses. Also, in the FP2/FP2SH/FP10SH, when a timer number or counter number has an index modifier, the
number of steps is the number in parentheses. For the FPΣ and FP-X, the number of steps varies according to the
specified timer number or counter number.