5-216
Num
-ber
Name
Boo-
lean
Ope-
rand
Description
Steps
FP-e
FP0
FP0R
FPΣ
FP-X
FP2
FP2SH/FP10SH
F136
P136
Number of
on (1) bits in
32-bit data
DBCU
PDBCU
S, D Store the number of on bits in the data of
(S+1, S) in “D”.
7
Basic function instruction
F137
Auxiliary
timer (16-bit)
STMR S, D Turn on the specified output and R900D
after 0.01 s × set value.
5
Special instructions
F138
P138
Hours, min-
utes and sec-
onds to
seconds data
HMSS
PHMSS
S, D Converts the hour, minute and second
data of (S+1, S) to seconds data, and
the converted data is stored in (D+1, D).
5
*1
F139
P139
Seconds to
hours,
minutes and
seconds data
SHMS
PSHMS
S, D Converts the seconds data of (S+1, S) to
hour, minute and second data,
and the converted data is stored in (D+1,
D).
5
*1
F140
P140
Carry flag
(R9009) set
STC
PSTC
- Turns on the carry flag (R9009).
1
F141
P141
Carry flag
(R9009) reset
CLC
PCLC
- Turns off the carry flag (R9009).
1
F142
P142
Watching
dog timer
update
WDT
PWDT
S The time (allowable scan time for the
system) of watching dog timer is
changed to “S” × 0.1 (ms) for that scan.
3
F143
P143
Partial I/O
update
IORF
PIORF
D1, D2 Updates the I/O from the number
specified by “D1” to the number specified
by “D2”.
5
F144
Serial data
communica-
tion control
TRNS S, n The COM port received flag (R9038) is
set to off to enable reception.
Beginning at “S”, “n” bytes of the data
registers are sent from the COM port.
5
*4
F145
P145
Data send SEND
PSEND
S1, S2,
D, N
Sends the data to another station in the
network (MEWNET). (via link unit)
9
F146
P146
Data receive RECV
PRECV
S1, S2,
N, D
Receives the data to another station
in the network (MEWNET). (via link unit)
9
F145
P145
Data send SEND S1, S2,
D, N
Sends the data to the slave station as
the MOD bus master. (via COM port)
9
*2
F146
P146
Data receive RECV S1, S2,
N, D
Receives the data from the slave station
as the MOD bus master. (via COM port)
9
*2
F145
P145
Data send SEND S1, S2,
D, N
Sends the data to the slave station of the
MOD bus master, type II.
9
*3
*3
F146
P146
Data receive RECV S1, S2,
N, D
Receives the data from the slave station
of the MOD bus master, type II.
9
*3
*3
F145
P145
Data send SEND S1, S2,
D, N
Sends the data to the slave station as
the MEWTOCOL master. (via COM port)
9
*2
*2
F146
P146
Data receive RECV S1, S2,
N, D
Receives the data from the slave station
as the MEWTOCOL master. (via COM
port)
9
*2
*2
F147
Printout PR S, D Converts the ASCII code data in the area
starting with “S” for printing, and outputs
it to the word external output relay WY
specified by “D”.
5
F148
P148
Self-
diagnostic
error set
ERR
PERR
n
(n: k100
to K299)
Stores the self-diagnostic error number
“n” in (DT9000), turns R9000 on, and
turns on the ERROR LED.
3
F149
P149
Message
display
MSG
PMSG
S Displays the character constant of “S” in
the connected programming tool.
13
: Available, : Not available, : Not available partially
*1) The instruction is available for FP0 T32 type (V2.3 or later).
*2) This instruction is available for FP-X V1.20 or later and FPΣ 32k type.
*3) This instruction is available for FP-X V2.50 or later and FPΣ V3.20 or later.
*4) This instruction is available for FP0 V1.20 or later.