High−level Instructions
3 − 324
Operation
When the reception completed flag (9038) is off and data is sent from an external device, operation will
proceed as follows. (After RUN, R9038 is off during the first scan.)
1) The data received is stored in order in the reception data storage area of reception buffer beginning
from the lower byte of the second word of the area.
Start and end codes will not be stored.
With each one byte received, the value in the leading address of the reception buffer is incremented
by 1.
AB
…
TUV(
C
R
)
Reception operation
start
Received data
Number of bytes
received
12 20 0120
R9038
Trigger R0
Reception
possible
…
…
…
Reception
possible
Reception
not
possible
Reopening
on
off
on
off
F144 (TRNS)
execution
2) When an end code is received, the reception completed flag (R9038) goes on. After this, no further
reception of data is allowed.
3) When an F144 (TRNS) instruction is executed, the reception completed flag (R9038) goes off and
the number of received data bytes is cleared to zero. Further data received is stored in order in the
reception data storage area beginning from the lower byte of the second word of the area.
Note
For repeated reception of data, refer to the following procedure 1)
to 5).
1) Receive data
2) Reception completed (R9038: on, Reception: not allowed)
3) Process received data
4) Execute F144 (TRNS) instruction (R9038: off, Reception: enable)
5) Receive further data