High−level Instructions
3 − 344
The SEND instruction only requests that the data be sent, but the actual processing takes place when
the ED instruction is executed.
The SEND/RECV execution end flag (R9045: COM1/R904B: COM2) can be used to check whether or
not the transmission has been completed.
R9045
(COM1)
0: Completed normally
1: Completed with error (The error code is stored in DT90124.)
DT90124
(COM1)
If the transmission has been completed with an error (R9045 is on), the contents of the error (error
code) are stored.
R904B
(COM2)
0: Completed normally
1: Completed with error (The error code is stored in DT90125.)
DT90125
(COM2)
If the transmission has been completed with an error (R904B is on), the contents of the error (error
code) are stored.
For information on the contents of error codes, refer to the manual. If the error code is H73, a communication
time−out error has occurred.
The time−out time can be changed within a range of 10.0 ms to 81.9 seconds (in units of 2.5 ms), using the
setting of system register 32.
The default value is set to 10 seconds.
Error code (HEX) Description
73 Time−out: Waiting for response
For global transmission (the transmission performed by specifying H00 for the unit No.), the program
should be set up so that the transmission is executed after a time of at least the maximum scan time
elapsed.
The F145 or F146 instruction cannot be executed if the target is a special internal relay (from R9000)
or a special data register (from DT9000).