High−level Instructions
3 − 359
Additional information concerning the F145 (SEND) instruction
Sending the special data registers and special internal relays using the data transfer instruction
Special data registers and special internal relays cannot be sent using the F145 (SEND) instruction. Use a
program like that shown below to send these types of data.
Sending FP2, FP2SH or FP10SH special data registers (source issuing the command: FP2/FP2SH/
FP10SH)
X10
F145 SEND, S, DT9****, DT0, Kn
10
Sending special internal relays (source issuing the command: FP2/FP2SH/FP10SH)
X10
F145 SEND, S, WR9**, DT0,Kn
10
How to send FL (How to specify FL banks)
How to specify the FL bank for destination units
The FL to communicate is specified like FL0 + H10. Specify FL1 + H10 to specify the FL of the bank 1
(FL2 + H10 for the bank 2)
How to specify the FL bank for a local unit
Normally, FLn is specified for the FL for the local unit. If specifying, the FL will be sent to the bank
which has been selected in the execution of this instruction.