High−level Instructions
3 − 405
Outline Writes data into the specified intelligent unit of the MEWNET-F slave
station.
Program example
Boolean
Ladder Diagram
Address Instruction
10
F153 RMWT, DT 0, DT 250, K 20, K 500
S1
S2
Trigger
R10
n
D
10
11
ST R 10
F153 (RMWT)
DT 0
DT 250
K20
K 500
S1 Lower 16-bit area of two 16-bit areas for storing control data of
F153 (RMWT)/P153 (PRMWT)
S2 Starting 16-bit area for storing data transferred to the shared memory
n 16-bit equivalent constant or 16-bit area for specifying number of data words
written
D 16-bit equivalent constant or 16-bit area for storing the starting address of the
shared memory in the intelligent unit
Operands
Relay Timer/Counter Register
Index
register
Constant
Inde
Operand
WX WY WR WL SV EV DT LD FL
IX
(*1)
IY
(*2)
K H
modifier
S1 A A A A A A A A A A N/A N/A N/A A
S2 A A A A A A A A A A N/A N/A N/A A
n A A A A A A A A A A A A A A
D A A A A A A A A A A A A A A
(*1) With the FP2, FP2SH, and FP10SH, this is I0 to IC.
(*2) With the FP2, FP2SH, and FP10SH, this is ID.
F153
P153
(PRMWT)
(RMWT)
Data write into MEWNET-F slave station
A: Available
N/A: Not Available