High−level Instructions
3 − 463
Flag conditions
・Error flag (R9007): Turns on and stays on when:
・Error flag (R9008): Turns on for an instant when:
− The area is exceeded when an index modifier is used.
− The “n” is outside specification range.
− The “S” is outside specification range.
− The “D” is outside specification range.
− The high−speed counter has not been set for the specified channel by the
system register.
FP0, FP−e
Channel No. Control flag Elapsed value area Target value area
ch0 R903A DT9044 to DT9045 DT9046 to DT9047
ch1 R903B DT9048 to DT9049 DT9050 to DT9051
ch2 R903C DT9104 to DT9105 DT9106 to DT9107
ch3 R903D DT9108 to DT9109 DT9110 to DT9111
FPΣ
Channel No. Control flag Elapsed value area Target value area
ch0 R903A DT90044 to DT90045 DT90046 to DT90047
ch1 R903B DT90048 to DT90049 DT90050 to DT90051
ch2 R903C DT91200 to DT91201 DT91202 to DT91203
ch3 R903D DT91204 to DT91205 DT91206 to DT91207
FP−X Ry type:ch0 to chB T type : ch0 to ch7 FP0R: ch0 to ch5
Channel No. Control flag Elapsed value area Target value area
ch0 R9110 DT90300 to DT90301 DT90302 to DT90303
ch1 R9111 DT90304 to DT90305 DT90306 to DT90307
ch2 R9112 DT90308 to DT90309 DT90310 to DT90311
ch3 R9113 DT90312 to DT90313 DT90314 to DT90315
ch4 R9114 DT90316 to DT90317 DT90318 to DT90319
ch5 R9115 DT90320 to DT90321 DT90322 to DT90323
ch6 R9116 DT90324 to DT90325 DT90326 to DT90327
ch7 R9117 DT90328 to DT90329 DT90330 to DT90331
ch8 R9118 DT90332 to DT90333 DT90334 to DT90335
ch9 R9119 DT90336 to DT90337 DT90338 to DT90339
chA R911A DT90340 to DT90341 DT90342 to DT90343
chB R911B DT90344 to DT90345 DT90346 to DT90347
FP0/FP−e/FPΣ/FP−X