High−level Instructions
3 − 686
Specifying the integer device with [D], the real numbers are automatically converted into integer data.
F311 F−, DT0, DT2, %DT4
R0
When the constant K is specified in S1 and S2, the operations are the same as when a integer device is
specified.
Program example
The “f0.445” is stored to DT30 and DT31 when the R0 turns on.
F311 F−, f1, f0.555, DT30
R0
The “f100.15” is stored to DT30 and DT31 when the R0 turns on.
R0
F309 FMV, f100.1, DT10
F309 FMV, f0.05, DT20
F311 F−, DT10, DT20, DT30
Precaution during programming
For FP0, this instruction F311 (F–) cannot be programmed in the interrupt program.
Flag conditions
・Error flag (R9007): Turns on and stays on when:
・Error flag (R9008): Turns on for an instant when:
− The area specified using the index modifier exceeds the limit.
− If data other than real number data is specified in “S1+1 and S1” and “S2+1
and S2.”
− If result of processing is outside integer range when integer device is
specified in D+1 and D.
・Carry flag (R9009): Turns on for an instant when the result is overflowed.