High−level Instructions
3 − 715
Outline Converts 32-bit integer data to floating point real number data.
For the FP0R/FPΣ/FP−X/FP0/FP−e, the P type high−level instruction
“P326 (PDFLT)” is not available.
Program example
Ladder
Diagram
Boolean
Ladder Diagram
Address Instruction
S
Trigger
D
F326 DFLT, DT10, DT2010
R0
10
11
ST R 0
F326 (DFL T)
DT 10
DT 20
S 32-bit integer data or lower 16-bit area of 32-bit data (source)
D Lower 16-bit area for 32-bit data floating point real number (destination)
Operands
O
p
erand
Relay Timer/Counter Register
Index
register
Constant
Index
modifier
Integer
device
Operand
WX WY WR WL SV EV DT LD FL I K H f
modifier device
S A A A A A A A A A A A A N/A A N/A
D N/A A A A A A A A A A N/A N/A N/A A N/A
Description
Converts the 32-bit integer data with sign specified by S to real number data when the trigger turns on. The
converted data is stored in D+1 and D.
32-bit integer
data with sign
15 0
D:
Floating point
real number
data
Lower word
D+1:
Higher word
15 0
S:
Lower word
S+1:
Higher word
Precaution during programming
For FP0, this instruction F326 (DFLT) cannot be programmed in the interrupt program.
F326
P326
(PDFLT)
(DFLT)
32-bit integer data → Floating point real number data
A
:
A
vailable
N/A: Not Available