Loading...
Program control RUN
1:00
2:00
200
0
0:30
1:00 2:00
300
(4) Write (Slave address 1, multiple pieces of program pattern data)
Program pattern setting example
Step 1 2 3 4 5
SV ( ) 200 200 300 300 0
Time 1:00 2:00 0:30 1:00 2:00
Wait value ( ) 10 0 10 0 0
(Fig. 5.6.2-1)
When writing the above program pattern, message data section converts to the following.
Amount of data: 15 (000FH)
Number of bytes: 30 (1EH)
Data: Data in the following table is converted to Hexadecimal.
Data Item Data Data (Converted to Hexadecimal)
1000H Step 1 SV 200 00C8H
1001H Step 1 time 60 minutes (1:00) 003CH
1002H Step 1 wait value 10 000AH
1003H Step 2 SV 200 00C8H
1004H Step 2 time 120 minutes (2:00) 0078H
1005H Step 2 wait value 0 0000H
1006H Step 3 SV 300 012CH
1007H Step 3 time 30 minutes (0:30) 001EH
1008H Step 3 wait value 10 000AH
1009H Step 4 SV 300 012CH
100AH Step 4 time 60 minutes (1:00) 003CH
100BH Step 4 wait value 0 0000H
100CH Step 5 SV 0 0000H
100DH Step 5 time 120 minutes (2:00) 0078H
100EH Step 5 wait value 0 0000H
A request message from the master (When writing the above program pattern data)
3.5 idle
characters
Slave
address
(01H)
Function
code
(10H)
Data item
(1000H)
1 1 2
Data
(000F1E00C8003C000A00C800780000012C001E000A012C003C0000000000780000H)
33
Error check
CRC-16
(13EEH)
3.5 idle
characters
2