MEWTOCOL
Modbus
Function
Code
Data Item Data
DT00220 03/06/10H 0078H Reserved (*2)
: : : :
DT00240 03/06/10H 008CH Reserved (*2)
DT00241 03/06/10H 008DH Control method 0000H : Usual PID
0001H : 2DOF PID
DT00242 03/06/10H 008EH Proportional gain 2DOF
coefficient (α)
Set value
DT00243 03/06/10H 008FH Integral 2DOF coefficient (β)
Set value
DT00244 03/06/10H 0090H Not used (*3)
: : : :
DT00323 03/06/10H 00DFH Not used (*3)
DT00324 03/06H 00E0H OUT/OFF key function 0000H : Control output OFF function
0001H : Auto/Manual control
0002H : Program control
DT00325 03/06H 00E1H Reserved (*2)
DT00326 03/06H 00E2H Control output OFF function
Auto/Manual control
Program control RUN/STOP
When Control output OFF function is
selected:
0000H: Control output ON
0001H: Control output OFF
When Auto/Manual control is
selected:
0000H: Automatic control
0001H: Manual control
When Program control is selected:
0000H: Program control STOP
0001H: Program control RUN
DT00327 03/06H 00E3H Program control
Holding/Not holding
0000H : Not holding
0001H : Holding
DT00328 03/06H 00E4H Output by communication
command
B0 EV1 output 0: OFF, 1: ON
B1 EV2 output 0: OFF, 1: ON
DT00329 03/06H 00E5H Manual control MV (*4) Set value
DT00330 03/06H 00E6H AT/Auto-reset Perform/Cancel 0000H : AT/AT on startup/
Auto-reset Cancel
0001H : AT/Auto-reset Perform
0002H : AT on startup Perform
DT00331 03/06H 00E7H Controller/Converter 0000H : Controller
0001H : Converter
DT00332 03/06H 00E8H AT gain Set value, Decimal point ignored
6.1.2 A Single Piece of Data Write Command
MEWTOCOL
Modbus
Function
Code
Data Item Data
DT00333 06H 00E9H
Program control
Advance function (*5)
0001H : Advance Perform
DT00334 06H 00EAH Not used (*3)
: : : :
DT00353 06H 00FDH Not used (*3)
DT00354 06H 00FEH Data clear (*6) 1234H : Clear data
DT00355 06H 00FFH Key operation change flag
clearing (*7)
0001H :