E13
--
E12
-
English
Wiring Maintenance/inspections
02
Connector
for control 
signals (I/O)
External speed setting 
Variable resister 5 kΩ 
B characteristic 1/4 W
Brushless
amplifier
change of
Direction 
10
1
01
+5V
FIN
GND
I3
I4
I5
I2
I1
Power 
supply
input
L1
L2
1
5
6
10
 Be sure to ground the grounding terminal. 
MCCB
Molded Case
(
Circuit Breaker
)
Grounding
Noise
filter
Brushless
amplifier
Power 
supply
input
L1
L2
1
5
6
10
 Be sure to ground the grounding terminal. 
MCCB
Molded Case
(
Circuit Breaker
)
Grounding
Noise
filter
Run/Stop
command
GV series
Forced trip
02
Connector
for control 
signals (I/O)
10
1
01
+5V
(NC)
GND
I3
(NC)
I4
I2
I1
• In case of single-phase 100 V/200 V
GP series
Run start
Point designation
Home sensor
In wiring to power supply (outside of equipment) from MCCB, use an electric wire of 1.6 mm 
diameter (2.0 mm
2
) or more both for main circuit and grounding. 
Apply grounding class D (100 Ω or below) for grounding. 
Do not tighten the ground wires together, but connect them individually.
Fastening torque of earth screws to be 0.49 to 0.98 N·m.
Routine  maintenance  and  inspection  are  essential for  proper and  satisfactory 
operation of the motor.
Notes to maintenance/inspection personnel
• Power-on/off operations should be done by the operators themselves for ensuring safety 
in checking.
• Do not touch the motor while it is running or immediately after it stops because it gets hot 
and stays hot for a while after power has been turned off.
•  When  testing  the insulation  resistance  of  the  brushless  amplifier with  the  megger, 
disconnect the amplier from all associated devices. Performing megger testing without 
rst disconnecting these devices will cause failure.
Maintenance/ Inspection item
Maintenance/
Check item
Inspection
procedure
Condition
Input voltage Voltmeter  Must be within ±10% of rating.
Input current Ammeter  Must be within rated input current described on nameplate.
Insulation
resistance
Insulation 
resistance 
tester 
The resistance of motor should be 1 MΩ or higher when tested 
with a 500 V megger.
Brushless motor: Across phase (U, V, W) and ground terminals
Noise  Hearing
Noise level must not be different from the usual level. In 
addition, abnormal noise such as rumbling noise must not be 
heard. 
Vibration By hand Free from abnormal vibration. 
Grease 
leakage
Visual check
Check that circumference of the motor and gear head are free 
from oil and grease.
If grease leakage will cause problem, use grease sealing cover.
Installation 
bolt 
Torque 
wrench 
Check for loosening of bolt, and tighten additionally as 
necessary. 
Use 
environment
By sight
Check the ambient temperature and humidity, and make sure 
that dirt, dust, or foreign substance is not found. 
When disassembly, troubleshooting, etc., is needed,
be sure to contact our service department or the sales agent of purchase.