20
Product description
3.3 System lineup
System lineup – ECOi systems
Capacity Outdoor unit combination AHU Kit combination
HP kW
5 16 all ECOi outdoor units PAW-160MAH2(L)
1
10 28 U-10ME1E81 PAW-280MAH2(L)
2
20 56 U-20ME1E81 PAW-560MAH2(L)
3
30 84 U-16ME1E81 U-14ME1E81 PAW-560MAH2(L) PAW-280MAH2(L)
40 112 U-20ME1E81 U-20ME1E81 PAW-560MAH2(L) PAW-560MAH2(L)
50 140 U-18ME1E81 U-16ME1E81 U-16ME1E81 PAW-560MAH2(L) PAW-560MAH2(L) PAW-280MAH2(L)
60 168 U-20ME1E81 U-20ME1E81 U-20ME1E81 PAW-560MAH2(L) PAW-560MAH2(L) PAW-560MAH2(L)
1 PAW-160MAH2(L):
PAW-160MAH2(L) can be installed in combination with all ECOi 2-pipe and 3-pipe outdoor units like
any other standard indoor unit.
Mixed installation with standard indoor units is possible. However, in this case one additional RAP
valve (CZ-P160RVK2) must be installed in the unit connection pipe, unless the unit is exclusively
used in cooling only operation.
2 PAW-280MAH2(L):
Mixed installation with standard indoor units is possible. However, in this case two additional RAP
valves (2 x CZ-P160RVK2) must be installed in the unit connection pipe, unless the unit is exclu-
sively used in cooling only operation.
Connection to ECOi 3-way systems is not allowed.
3 PAW-560MAH2(L):
Mixed installation with standard indoor units is not allowed.
Connection to ECOi 3-way systems is not allowed.
System lineup – ECO G systems
Capacity Outdoor unit AHU Kit
HP kW
5 16
all ECO G outdoor units
PAW-160MAH2(L)
1
10 28
all ECO G outdoor units
PAW-280MAH2(L)
2
20 56 U-20GE2E5 PAW-560MAH2(L)
3
1 PAW-160MAH2(L):
PAW-160MAH2(L) can be installed in combination with all ECO G outdoor units like any other stand-
ard indoor unit.
Mixed installation with standard indoor units is possible. However, in this case one additional RAP
valve (CZ-P160RVK2) must be installed in the unit connection pipe, unless the unit is exclusively
used in cooling only operation.
2 PAW-280MAH2(L):
PAW-280MAH2(L) an be installed in combination with all ECO G outdoor units like any other stand-
ard indoor unit.
Mixed installation with standard indoor units is possible. However, in this case two additional RAP
valves (2 x CZ-P160RVK2) must be installed in the unit connection pipe, unless the unit is exclu-
sively used in cooling only operation.
3 PAW-560MAH2(L):
With PAW-560MAH2(L), only 1-to-1 installations are allowed (1 x U-20GE2E5 + 1 x PAW-
560MAH2(L)). Combinations with more than 1 outdoor unit or more than 1 AHU Kit are not possible.
Mixed installation with standard indoor units is not allowed.