1
1-11-3
(B) When an obstruction is present on the air outlet side
When the upward area is open
(1) One outdoor unit installed individually (2) Two or more units installed side by side
*
a
a 500 mm or more
a
c
b
a 1,000 mm or more
b 250 mm or more
c 250 mm or more
* When also using the air-discharge chamber, provide a space of
500 mm or more.
When an obstruction is present also in the upward area
(1) One outdoor unit installed individually (2) Two or more units installed side by side
a
c
b
a 500 mm or more
b 500 mm or less
c 300 mm or more
a
c
b
e
d
a 500 mm or more
b 250 mm or more
c 250 mm or more
d 500 mm or less
e 1,000 mm or more
(C) When an obstruction is present on both the air inlet and air outlet sides
Case 1: When an obstruction on the air outlet side is higher than the outdoor unit (L
>
H)
(There is no height restriction on the air inlet side.)
When the upward area is open
(1) One outdoor unit installed individually (2) Two or more units installed side by side
*
a
b
H
L
a 100 mm or more
b 500 mm or more
a
b
d
c
H
L
a 200 mm or more
b 1,000 mm or more
c 250 mm or more
d 250 mm or more
* When using the air-discharge chamber, provide a space of 300 mm
or more.
When an obstruction is present also in the upward area (Do not use the air-discharge chamber.)
(1) One outdoor unit installed individually
a
A
c
L
H
b
a 200 mm or more
b 500 mm or less
c 1,000 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
L A
L
H
0
<
L
1/2H 300
1/2H
<
L
H 500
H
<
L Install the frame to achieve L
H.
Close the area under the frame so that the outlet air does
not bypass there.
01_301769_2WAY_eng.indb 12 2018/3/20 9:14:55
(B) When an obstruction is present on the air outlet side
When the upward area is open
(1) One outdoor unit installed individually (2) Two or more units installed side by side
a 500 mm or more a 1,000 mm or more
b 250 mm or more
c 250 mm or more
* When also using the air-discharge chamber, provide a space of
500 mm or more.
When an obstruction is present also in the upward area
(1) One outdoor unit installed individually (2) Two or more units installed side by side
a 500 mm or more
b 500 mm or less
c 300 mm or more
a 500 mm or more
b 250 mm or more
c 250 mm or more
d 500 mm or less
e 1,000 mm or more
(C) When an obstruction is present on both the air inlet and air outlet sides
Case 1: When an obstruction on the air outlet side is higher than the outdoor unit (L
>
H)
(There is no height restriction on the air inlet side.)
When the upward area is open
(1) One outdoor unit installed individually (2) Two or more units installed side by side
a 100 mm or more
b 500 mm or more
a 200 mm or more
b 1,000 mm or more
c 250 mm or more
d 250 mm or more
* When using the air-discharge chamber, provide a space of 300 mm
or more.
When an obstruction is present also in the upward area (Do not use the air-discharge chamber.)
(1) One outdoor unit installed individually
a 200 mm or more
b 500 mm or less
c 1,000 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
L A
L
H
0
<
L
1/2H 300
1/2H
<
L
H 500
H
<
L Install the frame to achieve L
H.
Close the area under the frame so that the outlet air does
not bypass there.
(2) Only two outdoor units installed side by side
b
a
A
c
L
H
a 200 mm or more
b 500 mm or less
c 1,000 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
L A
L
H
0
<
L
1/2H 500
1/2H
<
L
H 750
H
<
L Install the frame to achieve L
H.
Close the area under the frame so that the outlet air does
not bypass there.
Only two outdoor units can be installed side by side.
Case 2: When an obstruction on the air outlet side is lower than the outdoor unit (L
H)
(There is no height restriction on the air inlet side.)
When the upward area is open
(1) One outdoor unit installed individually (2) Two or more units installed side by side
a
b
L
H
*
a 100 mm or more
b 500 mm or more
d
c
a
b
L
H
a 100 mm or more
b 1,000 mm or more
c 250 mm or more
d 250 mm or more
* When using the air-discharge chamber, provide a space of
300 mm or more.
When an obstruction is present also in the upward area (Do not use the air-discharge chamber.)
(1) One outdoor unit installed individually
A
a
H
L
c
b
a 500 mm or more
b 500 mm or less
c 1,000 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
A
L
H 200
H
<
L Install the frame to achieve L
H.
Close the area under the frame so that the outlet air does
not bypass there.
(2) Only two outdoor units installed side by side
A
a
H
L
c
b
a 1,000 mm or more
b 500 mm or less
c 1,000 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
A
L
H 200
H
<
L Install the frame to achieve L
H.
Close the area under the frame so that the outlet air does
not bypass there.
Only two outdoor units can be installed side by side.