1
1-11-7
CHECK OF DENSITY LIMIT
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for installation space of
appliance are determined according to the refrigerant charge amount [m
c
] used in the appliance.
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows:
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Can be installed
Can not be installed
[m
c
] : the refrigerant
charge amount (
kg)
[Amin] : minimum indoor floor space (m
2
)
08.122.1
[m
c
] : The refrigerant charge amount (Total of refrigerant at shipment and refrigerant charge amount in the field).
[m
max
] : Maximum refrigerant charge amount
U-60PZ2R5
U-71PZ2R5
[m
max
] 1.80
[m
c
] ≤ 1.22 : Can be installed
1.22 < [m
c
] ≤ [m
max
] : Installation possible with in the range of slanted line part
[m
c
] > [m
max
] : Can not be installed
SM830266-00_大洋州向けR32シングルTD&SM.indb 7 18/03/29 10:20:08