1-5. Capacity Correction Graph According to Temperature Condition
U-100PZ2R5 (For 50 Hz), U-100PZ2R8 (For 50 Hz)
Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity)
Cooling Heating
Outdoor unit heating capacity correction cofficient during of frosting/defrosting (RH approximately 85%)
Outdoor intake air
temperature °C WB
-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -1.8 -0.8 0 1 2 3 4 5 6
Correction coefficient
0.88 0.88 0.87
-2
0.87 0.87 0.85 0.85 0.83 0.85 0.89 0.91 0.95 1.00.880.880.880.880.880.880.880.880.880.88
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
Capacity (kW) Capacity (kW)
0
20
40
60
80
100
120
140
160
180
86420 10 12 14
153%
200
22°CWB
19°CWB
16°CWB
40
60
80
100
120
140
Outdoor air intake temp ( °C WB)
Capacity coefficient (%)
40
60
80
100
120
140
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C DB)
16°CDB
20°CDB
24°CDB
16°CDB
20°CDB
24°CDB
-15-20 -10 -5 0 5 10 15 20
40
60
80
100
120
140
Outdoor air intake temp ( °C DB)
Capacity coefficient (%)Input coefficient (%)
Input coefficient (%)
Input coefficient (%)
40
60
80
100
120
140
Indoor air intake temp ( °C WB)
Indoor air intake temp ( °C WB)
0
20
40
60
80
100
120
140
160
180
86420 10 12 14 16
200
Input coefficient (%)
-10 0 10 20 30 40-5 5 15 25 35
192%
22°CWB
19°CWB
16°CWB