1-1-2
11
Single-Type
1-1. Unit Specifications
4-Way Cassette Type S-60PU2E5B / U-60PZ2R5
INDOOR MODEL
S-60PU2E5B - -
PANEL MODEL
Standard type:CZ-KPU3:ECONAVI type:CZ-KPU3A
- -
OUTDOOR MODEL
- U-60PZ2R5 -
Branch pipe MODEL
-
Performance test condition
ISO5151 / AS/NZS3823.1
Power supply
ø, Hz
1Ø 50Hz 1Ø 50Hz
V
- 230V 240V - 230V 240V Min Max
C
O
O
L
I
N
G
Capacity
kW
- 6.0 6.0 - - - 2.0 7.1
BTU/h
- 20500 20500 - - - 6800 24200
Current A
- 0.35 0.34 - 6.95 6.70 - -
Input power
W
- 38 38 - 1.442k 1.442k - -
TOTAL W
- - 1.480k 1.480k 300 2.000k
Annual consumption TOTAL kWh *
4
- - - - 740 - - -
EER/ AEER/ STAR RATING TOTAL (W/W/-)
- - - -
4.05/3.90/3
4.05 6.67 3.55
Power factor %
- - - - 90 90 - -
Noise indoor
dB-A (H/M/L) *
6
36/31/28 - - -
Power Level dB
51/46/43 - - -
Noise outdoor
dB-A (H/L)
- 46/- - -
Power Level dB
- 65/- - -
H
E
A
T
I
N
G
Capacity
kW
- 6.0 6.0 - - - 1.8 7.6
BTU/h
- 20500 20500 - - 6100 25900
Current A
- 0.34 0.33 - 5.85 5.60 - -
Input power
W
- 36 36 - 1.214k 1.214k - -
TOTAL W
- - 1.250k 1.250k 230 2.300k
COP/ ACOP/ STAR RATING TOTAL (W/W/-)
- - - -
4.80/4.59/4.5
4.80 7.83 3.30
Power factor %
- - - - 90 90 - -
Noise indoor
dB-A (H/M/L) *
6
36/31/28 - - -
Power Level dB
51/46/43 - - -
Noise outdoor
dB-A (H/L)
- 48/- - -
Power Level dB
- 66/- - -
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP
- -
Max Current (A) / Max Input power (W)
- 0.35/38 0.34/38 -
16.4/3.39k 16.4/3.54k
-
Starting current (A) / Comp output (W)
- - - -
6.95/1.7k
6.70/1.7k
-
Network Impedance (ΩMAX.)
- - -
Fan motor output (Indoor/Outdoor) W
60 60 -
Moisture removal volume L/h(Pt/h)
1.7 (3.6) - -
External static pressure Pa
- - -
Indoor
Air ow *6
Cooling m
3
/min (ft
3
/min)
21.0/16.0/13.0
(742)/(565)/(459)
- - -
Heating m
3
/min (ft
3
/min)
21.0/16.0/13.0
(742)/(565)/(459)
- - -
Outdoor
Air ow
Cooling m
3
/min (ft
3
/min)
- 45 (1589) - -
Heating m
3
/min (ft
3
/min)
- 45 (1589) - -
Refrigerant type / amount
g
(oz)
-
R32 1.45k (51.1)
-
Product dimension
Height mm(inch)
256 (10-5/64) 695 (27-23/64) -
Width mm(inch)
840 (33-5/64) 875 (34-29/64) -
Depth mm(inch)
840 (33-5/64) 320 (12-38/64) -
Product dimension (Panel)
H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
- -
Packing dimension
Height mm(inch)
302 (11-57/64) 761 (29-61/64) -
Width mm(inch)
898 (35-3/8) 1049 (41-19/64) -
Depth mm(inch)
898 (35-3/8) 460 (18-7/64) -
Weight
(NET) k
g
(lb)
20 (44) 44 (97) -
(GROSS) k
g
(lb)
27 (60) 49 (108) -
Panel (NET) k
g
(lb)
5 (11) - -
Layers limit (actually)
11 (12)
3 (4) -
Operation condition
Cool (DBT) 18°C ~ 32°C -10°C ~ 43°C
-
Heat (DBT) 16°C ~ 30°C -15°C ~ 24°C
-
MAX WORKING PRESSURE HP/LP MPa (bar) 4.15/2.55 (41.5/25.5)
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8) (Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
ared type, 5.0(16.4) ared type, 5.0(16.4) -
Pipe length range m (ft)
3 ~ 40m (9.8 ~131.2) -
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4) -
Add gas amount
g
/m (oz/ft)
35
g
/m (0.376) -
Pipe length for additional gas m (ft)
30m (98.4) -
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low"temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830266-00_大洋州向けR32シングルTD&SM.indb 2 18/03/29 10:19:21