16
Specications
Single Split Outdoor Unit (R32)
Europe
Model Name
U-36PZ3E5 U-50PZ3E5 U-60PZ3E5A U-71PZ3E5A
Power source 220 - 230 - 240 V
50 Hz
Cooling capacity
kW
3.6 5.0 6.0 7.1
BTU/h
12,300 17,100 20,500 24,200
Heating capacity
kW
3.6 5.0 6.0 7.1
BTU/h
12,300 17,100 20,500 24,200
Sound pressure level
(Cooling / Heating)
dB(A)
46 / 47 46 / 46 47 / 48 48 / 49
Sound power level
(Cooling / Heating)
dB(A)
64 / 66 64 / 64 64 / 65 66 / 68
Unit dimensions
(H×W×D)
mm
619×824×299 619×824×299 695×875×320 695×875×320
Net weight
kg
32 35 42 50
Operation condition temperature range
•Coolingmode:-10°C~43°CDB•Heatingmode:-15°C~24°CDB
Europe
Model Name
U-100PZ3E5 U-125PZ3E5 U-140PZ3E5 U-100PZ3E8 U-125PZ3E8 U-140PZ3E8
Power source 220 - 230 - 240 V
50 Hz 380 - 400 - 415 V 3N
50 Hz
Cooling capacity
kW
9.5 12.1 13.4 9.5 12.1 13.4
BTU/h
32,400 41,300 45,700 32,400 41,300 45,700
Heating capacity
kW
9.5 12.1 13.4 9.5 12.1 13.4
BTU/h
32,400 41,300 45,700 32,400 41,300 45,700
Sound pressure level
(Cooling / Heating)
dB(A)
52 / 52 55 / 55 56 / 56 52 / 52 55 / 55 56 / 56
Sound power level
(Cooling / Heating)
dB(A)
70 / 70 73 / 73 74 / 74 70 / 70 73 / 73 74 / 74
Unit dimensions
(H×W×D)
mm
996
×
980
×
370 996
×
980
×
370 996
×
980
×
370 996
×
980
×
370 996
×
980
×
370 996
×
980
×
370
Net weight
kg
83 87 87 83 87 87
Operation condition temperature range
•Coolingmode:-10°C~43°CDB•Heatingmode:-15°C~24°CDB
Rated conditions
Cooling : Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.
Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.
Outdoor unit