5 - 35
2. Detailed Settings Function
5
VRF SYSTEMS Indoor Unit
1-1. How to Set on PC Board
1. Turn off the power breaker to halt the supply of electricity to the PC board.
2. Open the lid of the electrical component box and confirm the location where the Select switch on the indoor unit control PCB is placed.
(Fig. 2-9)
3. Set the On/Off switches in the Off position which are now set in the On position.
Select the positions of the Select SW001 switches respectively to make the desired external static pressure settings referring to
the Table 2-8.
Table 2-8 External static pressure SW setting
External static pressure
at the time of rated
airflow volume
SW001
224 280 TP6 TP3 TP1
270Pa 270Pa
ON
1 2 3
140Pa 140Pa
1
ON
2 3
60Pa 72Pa
1 2
ON
3
Table 2-9 Setting the external static pressure
Indoor unit Item code
180, 224 280
External static pressure of the rated air
flow volume
270 Pa 270 Pa
140 Pa 140 Pa
60 Pa 72 Pa
6
2
1 5
1
4
3
NOTE:
Failure to set this parameter may result in decreased airflow
and condensation.
1-2. Operating the Timer Remote Controller
(CZ-RTC2)
How to set the external static pressure
1. Press and hold down the
, and buttons
simultaneously for 4 or more seconds.
( , the Unit No., Item Code and Detailed Data
will blink on the LCD display.)
2. The indoor unit numbers in the group control will
be sequentially displayed whenever the Unit Select
button is pressed
.
Only the fan motor for the selected indoor unit will
operate during this time.
3. Specify the “
item code by pressing the
/
buttons for the temperature set-
ting buttons and confirm the values.
(“ set at shipment )
4. Press the
/
buttons for the time to amend
the values for the set data.
Refer to Table 2-9 and Fig. 2-10 and select a value
”, “ ” or “ ”.
5. Press the
button.
The display will stop blinking and remain illuminat-
ed.
6. Press the
button. The fan motor will stop oper-
ating and the LCD display will return to the normal
stop mode.
1
ON
TP6
TP3
TP1
2
SW001
3
1
TP6
TP3
TP1
2
SW001
3
ON
Indoor Unit control PC board
Fig. 2-9