Design of 3WAY VRF SYSTEM
2 - 7
1
2
3
4
5
6
7
8
9
1. Model Selection and Capacity Calculator
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
Design of 2WAY SYSTEM
ID 64
L2
L2'
ID 1
ID 3 ID 4
ID 2
ID 63
1st distribution joint
OD 1OD 2OD 3
L2 ''
L4
2nd distribution joint
Refrigerant Tube
Tubing size increase [Difference L from the first distribution joint between maximum and minimum length]
If the L exceeds 131ft. (40m), it is necessary to increase both the liquid tube, suction tube and discharge tube by one size.
Follow the steps below to increase the size.
1. Check the combined indoor units which the
L exceeds 131ft. (40m).
Calculate the L of each combined indoor unit after 1st distribution joint (L2 {L2', L2'' ....} -L4).
The L2 ( L2 {L2', L2'' ....} ) indicates the tubing length connected to the farthest indoor unit among each combined indoor
unit from 1st distribution joint. The L4 indicates the tubing length connected from the 1st distribution joint to the nearest
indoor unit among all connected indoor units to the system. If the calculated L exceeds 131ft. (40m), it is necessary to
increase by one size of both the liquid tube, suction tube and discharge tube. Follow the steps to increase the size.
2. Check the total capacity of each combined indoor unit system.
Calculate the total capacity of indoor units from the 1st distribution joint.
Example: L2' L2'': Total capacity of indoor unit 3 and 4
3. Check the portion for increasing the tubing size and length.
Portion to increase the tube by one size: Increase the tubing size to be directed towards the indoor units from the 1st
distribution joint against the indoor unit which the L exceeds 131ft. (40m). Tubing length for sizing up: Tubing length
becomes different according to the total capacity of indoor units.
Total capacity of indoor units and tubing length for sizing up
Total capacity of combined indoor unitsLength for sizing up
Less than 76,400 BTU/h (22.4kW) 39ft. (12m)
More than 76,400 BTU/h (22.4kW) and less than 178,600 BTU/h (52.4kW) 66ft. (20m)
More than 178,600 BTU/h (52.4kW) 92ft. (28m)
* The larger the total capacity, the more it is necessary to increase the tubing length for sizing up.
* If the range of size up portion is improper, it is available to extend the length for sizing up until the next distribution joint
is reached.
NOTE:
1. Be sure to use the reducer (field supply) at joint portion between the original tube and the tube increased by one size.
2. If there is the necessity to increase by one size from the original tubing size, there can be only one time effective to
increase by one size even though the portion for sizing up is overlapped.
3. It may sometimes happen that the diameter of tube when sized up becomes wider than that of the main tube LA.
OD stands for outdoor unit.
ID stands for indoor unit.
7'B኱ὒᕞྥࡅ:$<B6HULHVLQGE 
*
5:
If the tubing length marked “L(L2 - L4) exceeds 131 ft. (40m), increase the tubing size at the portion after the 1st distribution joint by 1 rank
for the liquid tube, suction tube and discharge tube.
See the section “Refrigerant Tube” as described below.
*6:
7:
If any of the tubing length exceeds 98ft. (30m), increase the size of the tubes (liquid tube, suction tube and discharge tube)
between the distribution tube and solenoid valve kit by 1 rank and also increase the size of the tubes (liquid tube and gas tube)
between the solenoid valve kit and indoor unit by 1 rank.
* However, in the case of the Type 56 solenoid valve kit, it is not necessary to increase the tubes (liquid tube, suction tube and
discharge tube) between the distribution tube and solenoid valve kit by 1 rank.
If the size of suction tubes is ø1-5/8 in. (41.28mm), do not increase the size by 1 rank for the suction tubes.
Type 140
Type 56 Type 56Type 28
Type 140
L4: 99ft. (30m)
L2': 238ft. (72m)
Portion increased by
one size is overlapped
but only one size is
increased.
LF: 49ft.
(15m)
LH: 115ft. (35m)
LG: 180ft. (40m)
L2: 263ft. (80m)
Example 1
Example 2
1. Check the portion for one size increase.
ΔL Total capacity of indoor unitsLength for sizing up
L2 system 47,000 BTU/h (14kW) 39ft. (12m)
L2' system 94,000 BTU/h (28kW) 66ft. (20m)
L2 combined indoor units
Increase the discharge, suction and liquid tubes 39ft. (12m) by one size from the 1st distribution joint to be directed towards
LF: Increase 39ft. (12m) by one size among 49ft. (15m).
LG: No increase by one size
L2' combined indoor units
Increase the discharge, suction and liquid tubes 66ft. (20m) by one size from the 1st distribution joint to be directed towards
LF: Increase all 49ft. (15m) by one size
LH: Increase 16ft. (5m) by one size among 115ft. (35m).
2. Final result
Before sizing up
LF
ø1-1/8” / ø7/8” / ø1/2”
ø3/4” / ø5/8” / ø3/8”
ø3/4” / ø5/8” / ø3/8”
ø5/8” / ø1/2” / ø3/8”
ø7/8” / ø3/4” / ø1/2”
ø3/4” / ø5/8” / ø1/2”
ø7/8” / ø3/4” / ø3/8”
ø1-3/8” / ø1-1/8” / ø5/8”
ø1-1/8” / ø7/8” / ø1/2”
49ft. (15m)
LG
No size up
131ft. (40m)
LH 115ft. (35m)
49ft. (15m)
0 ft. (0m)
16ft. (5m)
* The LH is only 16ft. (5m) from the 2nd distribution joint.
* The size increased portion is overlapped at the LF but it has only one size increase.
L4: 33ft.
(10m)
L2: 197ft. (60m)
LF: 66ft. (20m)
1. Checking the portion for one size increase
Δ LTotal capacity of indoor unitsLength for sizing up
L2 system
238,000 BTU/h (70kW) 92ft. (28m)
L2 combined indoor units
Increase the discharge, suction and liquid tubes 92ft. (28m) by one size from the 1st distribution joint to be directed towards
LF: Increase 66ft. (20m) by one size.
LG: Increase 26ft. (8m) by one size among 33ft. (10m).
2. Final result
Before sizing up
LF 66ft. (20m)66ft. (20m)
LG 33ft. (10m) 26ft. (8m)
* The LG is only 26ft. (8m) from the 2nd distribution joint.LG
* It is possible to increase the LG to 33ft. (10m) by one size.
Outdoor
unit 1
Outdoor
unit 1
Outdoor
unit 2
Type 140 Type 140
164ft. (50m)
139ft. (42m)
After sizing up
Tube length
Size up length
LG: 33ft. (10m)
164ft. (50m)
After sizing up
Tube length
Size up length
L2 indoor units.
L2' indoor units.
L2 indoor units.
TD831183-00_北米向け3WAY.indb 7 15/12/17 16:05:07