Design of 3WAY VRF SYSTEM
2 - 46
1
2
3
4
5
6
7
8
9
8-2. Optional Distribution Joint Kits
Refer to the installation instructions packaged with the distribution joint kit for the installation procedure.
Table 15
Model name Cooling capacity after distribution Remarks
1. CZ-P900PH1U 307,100 BTU/h (90.0kW) or less For outdoor unit
2. CZ-P224BH1U 76,400 BTU/h (22.4kW) or less* For indoor unit
3. CZ-P680BH1U 232,000 BTU/h (68.0kW) or less* For indoor unit
4. CZ-P1350BH1U 460,700 BTU/h (135.0kW) or less* For indoor unit
Tubing size (with thermal insulation)
1. CZ-P900PH1U
For outdoor unit (Capacity after distribution joint is 307,100 BTU/h (90.0kW) or less.)
Note that the dimension marked with every alphabetical letter in the diagram shows the inner diameter.
11-13/16
(300)
11-13/16
(300)
(340)
13-25/64
D
C
B
FDE
C
C
H
I
HI
E
G
F
E
EFG
E
F
G
#C
C
E
D
DE
#C
D
#C
E
F
#C
Suction tube
Distribution
Joint
Insulation Insulation
Insulation
Discharge tube Liquid tube
*Insulators for both the Suction tube and the Discharge tube are the same.
* Suction tube and Discharge tube are similar in sizes and both the tube entrances have the same diameter. So the both
Distribution joints can fit into different tubes. Since the diameter of the tube ends for both Suction and Discharge tube are
different, take care not to connect the distribution joint different. See the “ # ” marks on the above figures.
Table 16 Dimensions for connections of each part
SizePart BPart CPart DPart EPart FPart GPart HPart I
Inch ø1-3/8 ø1-1/8 ø1 ø7/8 ø3/4 ø5/8 ø1/2 ø3/8
(mm) (ø34.92) (ø28.58) (ø25.4) (ø22.22) (ø19.05) (ø15.88) (ø12.7) (ø9.52)
Unit: in. (mm)
* In case the total capacity of indoor units
connected after distribution exceeds the
total capacity of the outdoor units, select
the distribution tube size for the total
capacity of the outdoor units.