EasyManua.ls Logo

Panasonic S-12MT2U6 - Page 43

Panasonic S-12MT2U6
181 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Design of 3WAY VRF SYSTEM
2 - 27
1
2
3
4
5
6
7
8
9
3. ELECTRICAL WIRING
Design of 3WAY VRF SYSTEM
Wiring sample
Wiring panel
(Front)
Wiring panel
(Bottom)
Electronic component box
Earth terminal *
3
Fit wires with cable clamps.
Fit power supply and Inter-unit
control wires with cable clamps
respectively (field supply).
Te rminal board for power supply
3P terminal board *
2
Inter-unit control wiring (U1, U2)
2P terminal board *
1
Inter-outdoor unit control wiring (1, 2)
2P terminal board *
1
Tightening torque
lbs.inch N · m
*1 11
31.25 0.25
*2 55
26.2 0.2
*3 73
48.2 0.4
Hollow to cut out opening *
4
Hollow to cut out opening Unit: in. (mm)*
4
ø1-3/4" (ø44) (Power supply wiring inserting port: knockout holes)
ø1-3/8" (ø35) (Power supply wiring inserting port: knockout holes)
ø7/8" (ø23) (Inter-unit control wiring inserting port: knockout holes)
ø1-3/8" (ø35) (Power supply wiring inserting port: knockout holes)
ø7/8" (ø23) (Inter-unit control wiring inserting port: knockout holes)
ø1-3/4" (ø44) (Power supply wiring inserting port: knockout holes)
*4
Hollow for jigsaw holes (Maximum allowed per hole is ø1-7/8" (ø48).)
Be sure to use waterproof conduit for electrical wiring to the outdoor unit.
Protective structure is necessary to avoid raindrops through wiring ports.
Hollow to cut out openings for wiring ports on the panel with a jigsaw.
3. ELECTRICAL WIRING
7'B໭⡿ྥࡅ:$<LQGE 
TD831183-00_北米向け3WAY.indb 27 15/12/17 16:05:13