Design of 3WAY VRF SYSTEM
2 - 65
1
2
3
4
5
6
7
8
9
8. Optional Parts
8-4-6-7. Single Floor Building Layout
Multiple type solenoid valve kit after the distribution joint is possible.
Outdoor
Single type
solenoid valve kit
Single type
solenoid valve kit
Multiple type
solenoid valve kit
Indoor
Indoor
Multiple type
solenoid valve kit
Single type
solenoid valve kit
La= Farthest indoor unit
0.49ft ≤ 0.49ft ≤
(0.15 m ≤ ) (0.15 m ≤ )
LbClosest Indoor unit
La-Lb ≤ 164ft (50m)
8-4-6-8. Multi Floor Building Layout
It is possible in terms of layout, however, be sure tubing diameter/tubing length, including the indoor units are within
the allowance.
Outdoor
Single type
solenoid valve kit
Multiple type
solenoid valve kit
Single type
solenoid valve kit
Multiple type
solenoid valve kit
Single type
solenoid valve kit
Single type
solenoid valve kit
Multiple type
solenoid valve kit
Single type
solenoid valve kit
8-4-6-9. Indoor unit control method
These control methods are possible.
Outdoor
Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor
Multiple type
solenoid valve kit
Distribution joint (*) Distribution joint (*)
Main Sub
Normal
control
Group control
by Main (+Sub) remo-con
Simultaneous operation
under 1port
(normal group control)
Individual operation under 1port
(Necessary special setting at initial
set-up for all indoor unit by PC.)
TD831183-00_北米向け3WAY.indb 65 15/12/17 16:05:28