22
3-24. Shape the Indoor Side Tubing
(1)  Arrangement of tubing by direction
  a)   Right or left tubing
   Cut out the corner of the right/left frame with a hacksaw 
or the like. (Figs. 3-89 and 3-90)
  b)   Right-rear or left-rear tubing
       In this case, the corner of the frame need not be cut.
(2)  To mount the indoor unit on the rear panel: 
   Hang the 3 mounting slots of the unit on the upper tabs 
of the rear panel. (Fig. 3-91)
3-25. Wiring Instructions
General precautions on wiring
(1)  Before wiring, confirm the rated voltage of the unit as 
shown on its nameplate, then carry out the wiring closely 
following the wiring diagram.
(2)  Provide a power outlet to be used exclusively for each 
unit, with a power supply disconnect and circuit breaker for 
overcurrent protection provided in the exclusive line.
(3)  To prevent possible hazards due to insulation failure, the 
unit must be grounded.
(4)  Each wiring connection must be done tightly and in 
accordance with the wiring system diagram. Wrong wiring 
may cause the unit to misoperate or become damaged.
(5)  Do not allow wiring to touch the refrigerant tubing, 
compressor, or any moving parts of the fan.
(6)  Unauthorized changes in the internal wiring can be very 
dangerous. The manufacturer will accept no responsibility 
for any damage or misoperation that occurs as a result of 
such unauthorized changes.
Fig. 3-89
Fig. 3-90
Fig. 3-91
Grille
Grille
Left tubing 
outlet
Right tubing 
outlet