Panasonic S-22ML1E5 - Selecting the Installation Site

Panasonic S-22ML1E5
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
100 cm
100 cm
100 cm
100 cm
100 cm
Fig. 2-1
20
cm
20
cm
100
cm
20
cm
100
cm
Fig. 2-2
Fig. 2-3
Fig. 2-4
Wall Mounted
2-Way Cassette
1-Way Cassette
Floor Standing, Concealed Floor Standing
Horizontal view
Vertical view
Front View
min. 100 cm
min. 100 cm
min.
100 cm
min.
100 cm
min. 15 cm
(min. 7.5 cm)*
min.
5 cm
min.
5 cm
45, 56, 73, 106 types
Part Name Figure Q’ty
Tapping screw
Truss-head
Phillips
4×20 mm
8
Tapping screw
Truss-head
Phillips
4×10 mm
2
Flare insulation
1
Table 1-4 (Floor Standing & Concealed Floor Standing)
Part Name Figure
Q
ty
Remarks
Connection
pipe
1
For connecting gas
tubes
Flare insulator
2
For gas and liquid
tubes
Insulating tape
(White)
2
For gas and liquid
tube flare nuts
Insulating tape
(Black)
2
For gas and liquid
tubes
Vinyl clamp
7
For ends of flare
insulator
Insulating tape
(black and long)
1
For drain pipe
Drain insulator
1 For drain hose joint
Use M12 for suspending bolts.
Field supply for suspending bolts and nuts.
2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room directly. This
may cause “sweating” on the air discharge ports, causing
them to spray or drip.
locations where the remote controller will be splashed with
water or affected by dampness or humidity.
installing the remote controller behind curtains or furniture.
locations where high-frequency emissions are generated.
DO:
select an appropriate position from which every corner of the
room can be uniformly cooled.
select a location where the ceiling is strong enough to
support the weight of the unit.
select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in the installation
instructions packed with the outdoor unit.
allow room for mounting the remote controller about 1 m off
the floor, in an area that is not in direct sunlight nor in the
flow of cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from the floor to the
ceiling is greater than 3 m (for D1 type, greater than 3.5 m).
* For 45, 56, 73, 106 types
PanaIndoor-337012Eng.indb7PanaIndoor-337012Eng.indb7 2012/03/2116:20:432012/03/2116:20:43