EasyManua.ls Logo

Panasonic S-36MK2E5A - Mini VRF Alarm Codes

Panasonic S-36MK2E5A
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 - 6
Mini VRF SYSTEM
Trouble Diagnosis
6
3. Mini VRF Alarm Codes
E06 Alarm
Alarm code
Alarm meaning
Alarm conditions
Probable cause
(2) An open circuit or short-circuit occurred in the inter-unit control wiring after initial
communications were completed.
Check
Correction
Example
Notes
E06
Some indoor units do not respond to outdoor unit.
Outdoor unit failed to receive serial communication signals from indoor unit.
(1) The indoor unit power was cut OFF after initial communications were completed.
Check the power at the indoor and outdoor units, and check the inter-unit control wiring.
This alarm is detected after initial communications are completed. Therefore, it does not occur in
cases of “disconnected serial connector,“no terminal unit set,or other trouble that occurs
before initial communications are completed. If initial communications have not been completed,
alarm E04 occurs.
E12 Alarm
Alarm code
Alarm meaning
Alarm conditions
Probable cause
Check
Correction
progress. Then start auto address setting again.
Example
Notes
E12
Auto Address failed to start.
Auto address setting was started when auto address setting was in progress at another outdoor
unit in the same link.
Auto address setting is in progress at another outdoor unit.
This alarm is not displayed on the remote controller. Therefore check the blinking on the Outdoor
Unit Control PCB.
Wait for auto address setting to be completed at the outdoor unit where it is currently in
E15 Alarm
Alarm code
Alarm meaning
Alarm conditions
Probable cause The number of indoor units set at the indoor unit quantity setting SW (SW3, SW4) on the
Outdoor Unit Control PCB is too many.
(2)
Check (1) See the section "7. TEST RUN" and check the indoor unit quantity setting SW (SW3, SW4).
(2)
The inter-unit control wiring between indoor units has been cut.
Check the inter-unit control wiring at the indoor and outdoor units.
Correction
address setting again.
Example
Notes
E15
Fewer indoor units are found in Auto Addressing than the setting on outdoor PCB.
The number of indoor units was too few when auto address setting was performed.
(1)
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform auto
Switch position
SW3SW4
12RI,8
SM830258-01_欧州向け_1fan_mini_VRF.indb 6 18/03/13 17:29:21

Table of Contents

Other manuals for Panasonic S-36MK2E5A

Related product manuals