EasyManua.ls Logo

Panasonic S-36MK2E5A - Indoor Unit MOV Control; Drain Pump Control

Panasonic S-36MK2E5A
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mini VRF SYSTEM
Control Functions - Indoor Unit
2 - 6
2
4. Indoor Unit MOV Control
5. Drain Pump Control
4. Indoor Unit MOV Control
For details, see the Section 1.
The MOV is at 480 pulses in the following cases.
At the time of factory shipment
Just after the indoor unit power cord is connected.
5. Drain Pump Control
The drain pump operates in the following conditions.
Cooling thermostat ON
The float switch worked.
The drain pump may often operate for a while when the cooling thermostat turns OFF or the indoor
unit is stopped.
The drain pump can be turned on when the cooling thermostat is OFF if the setting is made to prevent
water collected in the drain pan for a long time. For details, see the item "5-2. Detailed Settings
Function" under the Section 5.
The indoor unit heat exchanger liquid temperature (E1) is less than 0˚C when the cooling thermostat
is OFF or the indoor unit is stopped.
The drain pump operates for 20 minutes once it starts operating.
SM830258-01_欧州向け_1fan_mini_VRF.indb 6 18/02/09 10:54:36