Panasonic S-36MK2E5A - Detailed Settings in EEPROM of Outdoor Unit

Panasonic S-36MK2E5A
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 - 33
Mini VRF SYSTEM
Control Functions - Outdoor unit
1
11. Detailed Settings in EEPROM of Outdoor
Unit
Never use the DN code unlisted in the following table. (P) : Factory preset mode
DN Item Setting No.
05 Outdoor fan silent mode
0=Invalid (P) 1=Silent mode 1
2=Silent mode 2,,,,, 16=Silent mode 16
(For details, see "4. Outdoor Unit Fan Control (6)")
0C Indoor unit drain pump forced operation
0=Invalid
1=stop for 2 hours and drive for 20 minutes constantly
2=stop for 20 minutes and drive for 20 minutes constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
(For details, see "5. Outdoor Unit CCU Control (4)")
0D
Measures against smell when indoor unit cooling
thermostat OFF
0=Invalid (P)
1=Measures against smell
1A Demand 1 current (%)
0=0% 40=40%
45=45%,,,,, 100=100% (P) ,,,,,
160=160% -1=No control
(For details, see "9. Demand Control")
1B Demand 2 current (%)
0=0% 40=40%
70=70% (P),,,,, 100=100% ,,,,,
160=160% -1=No control
(For details, see "9. Demand Control")
1E Demand remote controller display
0=No demand display
1=When demand ON, “ready to start” display (P)
2=When forced thermostat OFF with demand ON,
“ready to start” display
(For details, see "9. Demand Control")
23 E06 ignore function
-1=Invalid (P) 0=0
1=1 ,,,,, 13=13
14 - 52=Never use
(For details, see "10. Other Functions")
27 Auto change over function for mini VRF system
0=Invalid (P) 30=30 minutes
40=40 minutes 50=50 minutes
60=60 minutes 90=90 minutes
120=120 minutes 180=180 minutes
240=240 minutes
(For details, see "10. Other Functions (1)")
2B DP operation time for slime measures
20=20 minutes 30=30 minutes (P)
40=40 minutes 50=50 minutes
60=60 minutes
(For details, see "5. Outdoor Unit CCU Control (4)")
2C Indoor unit fan stop temperature shift -30=-30°C,,,,, 0=+0°C (P) ,,,,,50=+50°C
35
Condensation temperature adjustment
Lower temperature of B area (Tc_B) for heating mode
-7=-7°C -6=-6°C,,,,, 0=0°C (P) ,,,,, 7=7°C
36
Condensation temperature adjustment
Upper temperature of B area (Tc_B) for heating mode
-7=-7°C -6=-6°C,,,,, 0=0°C (P) ,,,,, 7=7°C
3E PSccutgt delay-start setting
0=8 second delay-start (P)
1=(system address x1x8) second delay-start
2=(system address x2x8) second delay-start
3=(system address x3x8) second delay-start
3F Evaporating temperature control lower limit shift -9=-9°C,,,,,0=0°C (P), 1=1°C,,,,,20=20°C
40 Evaporating temperature control upper limit shift -9=-9°C,,,,,0=0°C (P), 1=1°C,,,,,20=20°C
51
Indoor unit fan's intermittent operation and operating
time when in cooling thermostat OFF
30=30 seconds , 60=60 seconds (P) ,,,, 240=240 seconds
52
Indoor unit fan's intermittent operation and stopped
time when in cooling thermostat OFF
5=5 minutes (P), 10=10 minutes, 15=15 minutes, 20=20 minutes,
25=25 minutes, 30=30 minutes
5F Highefciencymodesetting
0=Invalid (P), 1=Valid
(For details, see "4. Outdoor Unit Fan Control (8)")