Mini VRF SYSTEM
Control Functions - Outdoor unit
1 - 32
(3) Setting when at Thermostat OFF in Cooling Mode
WhendecreasingtheindoorairowvolumeatthecoolingthermostatOFFordrythermostatOFF,followthesetting
procedure below.
EEPROM setting in main outdoor unit
CODE: ED
Setting No. Indoor fan mode
Indoor unit
expansion valve
Louver
0 (factory preset mode) w/o force w/o force w/o force
1 STOP *3 20 w/o force
2 LL 20 w/o force
3 Interval mode *4 20 w/o force
4 Never use - -
*1 If setting at thermostat ON, the system will return to the normal indoor fan control or solenoid valve kit mode.
*2 Whenever changing thermostat ON and OFF, solenoid valve kit sounds ON and OFF.
*3 When setting at Stop mode, be sure to set the room sensor to the remote control thermostat.
EEPROM setting in indoor unit
CODE: 32
Setting No.
0 Indoor unit sensor (factory preset mode)
1 Remote control sensor
*4Operationwhenintheintermittentairowsetting
•WheninthethermostatOFF,LLairowandstopmoderepeatsalternatelyandthemechanicalvalveand
solenoid valve kit remain in the forced condition.
•IntervalintermittentoperationcanbechangedbyEEPROMsetting.
EEPROM setting in indoor unit
CODE: 51
Setting No.
Indoor unit fan operating
time [sec]
30 30
60 (factory preset mode) 60
90 90
…
…
210 210
240 240
CODE: 52
Setting No.
Indoor unit fan stopped
time [min]
5 (factory preset mode) 5
10 10
15 15
20 20
25 25
30 30
SM830258-01_欧州向け_1fan_mini_VRF.indb 32 18/03/06 9:09:53