33
Menu Default Setting Setting Options / Display 
To select a bivalent connection 
to allow an additional heat 
source such as a boiler to heat-
up the buffer tank and domestic 
hot water tank when heatpump 
capacity is insuffi cient at low 
outdoor temperature. The 
bivalent feature can be set-up 
either in alternative mode 
(heatpump and boiler operate 
alternately), or in parallel 
mode (both heatpump and 
boiler operate simultaneously), 
or in advance parallel mode 
(heatpump operates and boiler 
turns on for buffer-tank and/or 
domestic hot water depending 
on the control pattern setting 
options).
 
 Yes   Auto
-5 °C
Set outdoor 
temperature for 
turn ON Bivalent 
connection.
Yes   After selecting the outdoor temperature
Control pattern
Alternative / Parallel / Advanced parallel
• Select advanced parallel for bivalent use of 
the tanks.
Control pattern 
 Alternative
OFF
Option to set external
pump either ON or 
OFF during bivalent 
operation. Set to ON 
if system is simple 
bivalent connection.
Control pattern   Advanced parallel
Heat Selection of the tank
• “Heat” implies Buffer Tank and “DHW” 
implies Domestic Hot Water Tank.
Control pattern 
 Advanced parallel   Heat   Yes
• Buffer Tank is activated only after selecting 
“Yes”.
-8 °C
Set the temperature 
threshold to start the 
bivalent heat source.
0:30
Delay timer to start 
the bivalent heat 
source 
(in hour and minutes).
-2 °C
Set the temperature 
threshold to stop the 
bivalent heat source.