EasyManua.ls Logo

Panasonic WH-UD07CE5-A - Page 117

Panasonic WH-UD07CE5-A
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
117
17.5.23. Four Way Valve Abnormality (F25)
Malfunction Decision Conditions:
1. During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C.
2. During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C.
Malfunction Caused:
1. Faulty sensor.
2. Faulty connector connection.
3. Faulty outdoor unit PCB (noise filter/main).
4. Faulty four way valve.
Abnormality Judgment:
Continue 4 times in 30 minutes.

Table of Contents

Other manuals for Panasonic WH-UD07CE5-A

Related product manuals