EasyManua.ls Logo

Panasonic WH-UD07CE5-A - Page 99

Panasonic WH-UD07CE5-A
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
99
17.5.5. Water Flow Switch Abnormality (H62)
Malfunction Decision Conditions:
During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to determine water flow
error.
Malfunction Caused:
1. Faulty water pump.
2. Water leak in system.
3. Faulty connector connection.
4. Faulty water flow switch.
5. Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 10 seconds (but no judgment for 9 minutes after compressor startup/restart).

Table of Contents

Other manuals for Panasonic WH-UD07CE5-A

Related product manuals