19
ENGLISH
Optional cables:
External control cable
Outdoor air sensor cable
Remote controller cable
Room sensor zone 1 cable
Room sensor zone 2 cable
Buffer tank sensor cable
Pool sensor cable
Water sensor zone 1 cable
Water sensor zone 2 cable
Demand signal cable
Solar sensor cable
SG signal cable
Heat/Cool switch cable
External Compressor switch cable
Optional cables:
2-way valve cable
Extra pump cable
Boiler contact cable
Power Supply 1 cord
Power Supply 2 cord
Indoor Unit/Outdoor
Unit Connecting cable
Optional cables:
Pump zone 1 cable
Pump zone 2 cable
Solar pump cable
Pool pump cable
Room thermostat zone 1 cable
Room thermostat zone 2 cable
Mixing valve zone 1 cable
Mixing valve zone 2 cable
from Optional
PCB
from Optional PCB
Terminal screw on PCB Maximum tightening torque cN•m {kgf•cm}
M3 50 {5.1}
M4 120 {12.24}
Connecting Cables Length
When connecting cables between Tank Unit and external devices,
the length of the said cables must not exceed the maximum length
as shown in the table.
External device Maximum cables length (m)
Two-way valve 50
Mixing valve 50
Room thermostat 50
Extra pump 50
Solar pump 50
Pool pump 50
Pump 50
Boiler contact 50
External control 50
Room sensor 30
Outdoor air sensor 30
Buffer tank sensor 30
Pool water sensor 30
Solar sensor 30
Water sensor 30
Demand signal 50
SG signal 50
Heat/Cool switch 50
External compressor switch 50
Connection of the main PCB
Zone 1 room sensor
Outdoor air sensor
Tank sensor
External control
Remote controller
Boiler contact /
Defrost Signal
Extra pump
H C N LC O N C O N
Optional
Thermostat 1
3-way
valve
2-way
valve
Signal inputs
Optional Thermostat
L N =AC230V, Heat, Cool=Thermostat heat, Cool
terminal
It does not function when using the Optional PCB
External control
Dry contact Open=not operate, Short=operate
(System setup necessary)
Able to turn ON/OFF the operation by external
switch
Remote controller
Connected (Please use 2 cores wire for relocation
and extension. Total cable length shall be 50m
or less.)
Outputs
3-way valve
AC230V N=Neutral Open, Close=direction (For
circuit switching when connected to DHW tank)
2-way valve
AC230V N=Neutral Open, Close (Prevent water
circuit pass through during cooling mode)
Extra pump
AC230V (Used when Tank Unit pump capacity is
insuffi cient)
Boiler contact Dry contact (System setup necessary)
Thermistor inputs
Zone 1 room
sensor
PAW-A2W-TSRT
It does not work when using
the Optional PCB
Outdoor air
sensor
AW-A2W-TSOD (Total cable length shall be 30m
or less)
Connection of Optional PCB (CZ-NS4P)
Ext.
comp.
SW
Heat/
Cool
SW
SG
signal
Vcc
Bit1
Bit2
Solar
sensor
Mixing
valve 2
Mixing
valve 1
Optional
Thermostat 2
Optional
Thermostat 1
Demand
signal
Zone 1
water
sensor
Zone 2
water
sensor
Pool
water
sensor
Buffer
Tank
sensor
Zone 1
room
sensor
Zone 2
room
sensor
Zone 1
Pump
Error
signal
Pool
Pump
Solar
Pump
Zone 2
Pump
N O CN O CL N Cool Heat L N Cool Heat