29
ENGLISH
12. External Error Signal
Initial setting: No
System setup
12:00am,Mon
Bivalent connection
External SW
Solar connection
External error signal
Select Confi rm
Set when external error display unit is installed.
Turn on Dry Contact SW when error happened.
(NOTE) Does not display when there is no Optional PCB.
When error occurs, error signal will be ON.
After turn off “close” from the display, error signal will still remain ON.
13. Demand control
Initial setting: No
System setup
12:00am,Mon
External SW
Solar connection
External error signal
Demand control
Select Confi rm
Set when there is demand control.
Adjust terminal voltage within 1 ~ 10 V to change the operating current limit.
(NOTE) Does not display when there is no Optional PCB.
Analog input
[v]
Rate
[%]
Analog input
[v]
Rate
[%]
Analog input
[v]
Rate
[%]
0.0
not activate
3.9 ~ 4.1 40 7.4 ~ 7.6 75
0.1 ~ 0.6 4.2
45 40
7.7
80 75
0.7
10
not
activate
4.3 7.8
0.8 4.4 ~ 4.6 45 7.9 ~ 8.1 80
0.9 ~ 1.1 10 4.7
50 45
8.2
85 80
1.2
15 10
4.8 8.3
1.3 4.9 ~ 5.1 50 8.4 ~ 8.6 85
1.4 ~ 1.6 15 5.2
55 50
8.7
90 85
1.7
20 15
5.3 8.8
1.8 5.4 ~ 5.6 55 8.9 ~ 9.1 90
1.9 ~ 2.1 20 5.7
60 55
9.2
95 90
2.2
25 20
5.8 9.3
2.3 5.9 ~ 6.1 60 9.4 ~ 9.6 95
2.4 ~ 2.6 25 6.2
65 60
9.7
100 95
2.7
30 25
6.3 9.8
2.8 6.4 ~ 6.6 65 9.9 ~ 100
2.9 ~ 3.1 30 6.7
70 65
*A minimum operating current is applied on each model for
protection purpose.
*0.2 voltage hysteresis is provided.
*The value of voltage after 2nd decimal point are cut off.
3.2
35 30
6.8
3.3 6.9 ~ 7.1 70
3.4 ~ 3.6 35 7.2
75 70
3.7
40 35
7.3
3.8
14. SG ready
Initial setting: No
System setup
12:00am,Mon
Solar connection
External error signal
Demand control
SG ready
Select Confi rm
Switch operation of heat pump by open-short of 2 terminals.
Setting belows are possible
SG signal Working pattern
Vcc-bit1 Vcc-bit2
Open Open Normal
Short Open Heat pump and Heater OFF
Open Short Capacity 1
Short Short Capacity 2
Capacity setting 1
- DHW capacity ___%
Set by SG ready setting of remote controller
- Heating capacity ___%
- Cooling capacity ___°C
Capacity setting 2
- DHW capacity ___%
- Heating capacity ___%
- Cooling capacity ___°C
(When SG ready set to YES, Bivalent control pattern will set to Auto.)