EasyManuals Logo

Paradox Matrix2000 User Manual

Paradox Matrix2000
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
6
7
Matrix2000 - Advanced Analog Fire Alarm Control Panel
6
7
2.3 Additional system fault indications
In this group three distinct fault conditions are indicated:
2.3.1 SIGNALING DEVICE fault
When active, this indicator signies a fault condition of the signaling device output. The
fault can be one of the following:
Short circuit of the two output wires
Open circuit in the connecting cable between the block connector and the signaling
device. The signaling device must be terminated with a 4.7K Ohm resistor (EOL)
Blown fuse that protects the system from shorts while the signalling device is in
operation.
2.3.2 EARTH fault
When active, this indicator signies a short circuit between any of the panel’s wiring
(zones, relays, outputs etc.) and the building’s earth is detected.
The signaling device output wires are also monitored for the earth short condition.
2.3.3 AUX POWER Fault
When active, this indicator signies an overcurrent condition at the auxiliary power out-
put is detected. The maximum allowed current is 1 Amp. The device is capable of con-
tinuous operation even at full short circuit of this output; though any device powered from
this output will stop functioning.
If more than 1 Amp is required, a compatible EN 54-4 approved re alarm power supply
must be used. When such a power supply is used, the -24 OUT connection of the panel
must be connected to the negative terminal of the auxiliary power supply.
2.4 Zone Fault indications
The Zone Fault indications will blink, in a different pattern, (Figure 2, page 6) depending
on the type of the problem that occurs.
In detail:
(a) If a short-circuit or an opening of a zone is detected, System FAULT indication will
turn ON, the corresponding Zones FAULT indication will blink as in Pattern A, (Figure 2,
page 6) and at the same time there will be an audible notication from the on board
Buzzer.
Possible causes of a zone problem are:
(a1) Disconnection or interruption of wiring of the zone.
(a2) Short-circuit in the wiring of the zone.
(a3) Removal of sensor from its base.
(a4) Removal of the terminating resistor (EOL).
(b) When a Relay expansion module is used the Zones FAULT indication is also trig-
gered by:
A short-circuit or opening of the wiring in the corresponding zone relay output.
Removal of the output terminating resistor (EOL).
In case (b) as listed above the System FAULT indication will turn ON and the Zones
FAULT indication of the corresponding zone will blink (Figure 2, Pattern b). At the same
time there is also an audible notication from the on board Buzzer.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Paradox Matrix2000 and is the answer not in the manual?

Paradox Matrix2000 Specifications

General IconGeneral
BrandParadox
ModelMatrix2000
CategorySmoke Alarm
LanguageEnglish

Related product manuals