200 22
.8.3 Technical data
Model
Weight
Refrigerant
R407c (Kg)
MIN.- MAX
Ambient Temperature
Amb
Compressed
air inlet
Temperature
Air - Side
Max
Working
Pressure
Connections
Sound
pressure level
Compressed
air inlet/outlet
Condensate drain
During transport
and stockage
A er
installation
(lb) (Kg) (oz) (Kg)
In
[dB (A)]
200
172 78 45,8 1,3
32-122° F
0-50°C
41-122°F
5-50°C
41 - 149°F
5 - 65°C
203 PSIg
14bar
1.1/2” NPT - F 1/2” NPT - F 55
Model
Electrical
supply inlet
Compressor
1
M1
Fan motor
3
EV1
Minimum
circuit ampacity
MCA
(A)
Maximum
protection device
rating
HACR
(A)
Minimum section
validated cable for
electrical connections
Ø
RLA
(A)
LRA
(A)
RLA
(A)
LRA
(A)
200
230/1/60 7,5 24 0,6 0,14 7,8 10 14AWG
Calibration values Hot gas valve
9-HGV
Fan pressure Switch
12-PV
High pressure switch
15-HP1
High temperature thermostat
16-ST
200
66.7 - 69.6 PSIg
4.6 - 4.8 barg
ON: 261 PSIg
OFF: 203 PSIg
ON: 18 bar
OFF: 14 bar
406 PSIg
28 barg
248°F
120°C