200 3
English
5 Control
5.1 Control panel
2
3
4
5
6
1
1
&
MAIN SWITCH I ON = dryer operating; O OFF = dryer o
2
;
MAINTENANCE LED Scheduled maintenance
3
(
WARNING LED
Flashing = Dew point too low
Fixed = Dew point too high
4
)
DEW POINT LED
Flashing = Dew point slightly high
Fixed = Dew point correct
5
*
DRAIN LED Darin open
6
+
DRAIN BOTTON Drain opening control
5.2 Operation
Scheduled maintenance
! When
;
comes on, contact authorized assistance personnel for
carrying out scheduled maintenance
Press
+
so that
;
switches o for 24 hours.
Condensate drain
ere are two operating modes:
a) TIMED - with draining at xed intervals (2 minutes) and settable
time (1-10 seconds);
b) EXTERNAL: - if there is an external drain.
To change operating mode, switch the unit o , keep pressed
+
and
switch the machine on at the same time.
In EXTERNAL mode
*
is always on.
!
Set mode b) only in absence of the solenoid valve: otherwise
the relative coil could be come damaged.
In TIMED mode, during draining
*
ashes for a number of seconds
equal to the set time. For manual opening of the drain, press .
+
To change the draining time, keep pressed
+
until
;
comes on.
Release
+
and press again only once within 2 seconds.
*
will ash
once every second for 10 seconds. During ashing, press
+
once to
stop and store the count of seconds equal to the required draining time.
Remote alarm (option)
A relay (KA1) is provided to signal if there is power onto the unit and
an interface module (KA2) supplies a signal as shown in 8.8 of a high
dew point alarm.