IQAN-XT2 Technical Overview
Appendix A
Instruction book, IQAN-XT2
Recommended Operating Conditions
a
a.Recommended operating conditions are given for maximum and minimum conditions where nor-
mal performance is still available from the device. Once the normal operating conditions are exceed-
ed, the performance of the device may suffer.
Parameter
Limit values
Unit Remark
min. typ. max.
Ambient temperature, T
A
– 40 +70 °C
Voltage supply, V
BAT
11 32 V
Total load on COUT/PWMOUT/DOUT 20 A
System
T
A
= +25 °C (unless otherwise specified)
Parameter
Limit values
Unit Remark
min. typ. max.
Start-up delay TBD ms Power to activated output
Dither frequency, DF 25 150 Hz
Sample rate local I/O. 20 Hz Dependent of the CAN
sample time, exception
FIN channels.
CAN message response time TBD ms
Output voltage on VREF 4.9 5.0 5.1 V load < 40mA
Maximum load current on VREF
V
BAT
=11V to 32V
50 mA Vdrop < TBDmV (0.5%)
Current supply
V
BAT
=14V
V
BAT
=28V
140
160
mA
outputs = off
no load on VREF
I/O
T
A
= +25 °C (unless otherwise specified)
Parameter
Limit values
Unit Remark
min. typ. max.
VIN (Voltage input)
Signal range low 0 0.05 V
Signal range high 4.9 5.0 5.1 V
Input resistance 62 kΩ
Signal resolution 5 mV
Total unadjusted error -35
-100
35
100
mV VREF as source <40mA
External source
DIN (On/off input)
a
Input signal low 0.8 V
Input signal high 4.0 V
input hysteresis 1.0 V DIN-A -DIN-J
Input resistance 62 kΩ