9.3 TECHNICAL DATA
7
PSE 120-350
Model
Weight
Refrigerant
R513A
of
coolers
MIN.- MAX
Ambient Temperature
Amb
Compres-
sed
air inlet
Tempera-
ture
In
F.L.A.[A]
400V±10%/
3Ph/50Hz
460V±10%/
3Ph/60Hz
MOP MCA
Minimum
section
validated
cable for
electrical
connection
Connections
Sound
pressure
level
Compressed
air
inlet/outlet
Water
condensation
inlet/outlet
Condensate
drain
During
transport
and
stockage
After
installa-
tion
50Hz 60Hz
Kg Kg CO
2
e
(t) °C °C °C A A A Ø [mm2]
50Hz
BSPP-F
BSP-F [dB (A)]
PSE 120
205 1,9 1,09
1 0-50 5-50 5-65
6.54 6.6 10 8.5
4G2.5
2" -
1/2" <75
PSE 140
205 1,9 1,09
PSE 180
210 1,7 0,97 6.8 6.9 10 8.5
PSE 220
260 2.5 1.43 9.3 9.4 15 11.5
2".1/2
3/4"
PSE 260
262 2,5 1.43
10.6 10,7
20 13
PSE 300
264 2,5 1.43 20 13
1"
PSE 350
270 2,5 1.43 13.8 13.9 25 17 4G4
Calibration values
Hot gas valve
12 - HGV
Pressure condensation
High pressure Switch
13-HP
Low pressure Switch
9-LP
Air - Side Max
Working Pressure
IP
Pressure
Fan
speed
PSE 120/180
2.4-2.6 bar
10 bar
13 bar
0 %
100 %
20 bar 1.0-2.0 bar 14 bar
44
PSE 220/350
54

Table of Contents

Related product manuals