14
IA VRD UK.INDD RH 02.06
Digital Power Amplifier
Series VRD350 and VRD355Installation Manual
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
Transfer contents
Value is transfered. The
previously selected address
appears again.
Programming Instructions for H-Values
(Command Signal Simulation)
Select mode
Select mode U1
Select mode H1
First press key "E", then
press key "M" simultane-
ously.
Select address
Display, alter, transfer
contents
Select new address or return to mode U1 with the "M"-key.
Basic Settings
All parameters are preset ex-works according to the
intended application of the amplifier. This setting
depends on the type of amplifier (see also type
code). This basic setting can be recovered from
memory by pressing the 4 keys at the same time up
to 10 seconds after the supply voltage is switched
on. During recovery the display shows “HHH“.
After leaving H mode, auxiliary com-
mand signals are no longer utilized but
remain in the background. They must be
set back to zero after commissioning.
After supply voltage is disconnected, H parameter
settings are lost.
H1 or H2
Same procedure as for U, S and P-values. See
previous page
Setting parameters does not alter the preset values.
Customized parameters are overwritten by the re-
covery operation. Further information on adjusting
the basic settings can be found in the instructions
for the control program PROVRD 350/355.