EasyManua.ls Logo

Parker VRD355 Series - P-Parameters

Parker VRD355 Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital Power Amplifier
Series VRD350 and VRD355Installation Manual
21
IA VRD UK.INDD RH 02.06
Parker Hannifin GmbH & Co. KG
Hydraulic Controls Division
On leaving the H mode, H parameter values are
no longer evaluated and thus are deactivated.
However, H parameter values are also internally
stored after leaving the H mode.
When H mode is selected again (always
H1 first), this is immediately effective,
with its corresponding value. It is rec-
ommended, therefore, that H1 and H2
parameters are set to 0.00 when commissioning
has been completed. The H-parameters are set =
0.00 when the supply voltage is switched off.
Display
H1...H2
Command signal simulation
Command signals as voltage 0...±9.99V
P-Parameters
Parameters can be set during operation. Any altera-
tion to P-Parameters with and keys is immedi-
ately effective. These parameters allow the amplifier
unit to be matched to the valve or the drive.
Display
P1 Offset (+30%... -30%) 0.00...+2.99
(See also page 25, section 3.3) 0.00...-2.99
Steps in 5 mV
Display in 10 mV steps
P2 Linearisation
Not active 0
Active 1...5
when using NC, select a linearisation!
(See also page 25, section 3.4)
P3 Gain factor for solenoid A
0.00...2.00
(See also page 25, section 3.5)
P4 Gain factor for solenoid B
0.00...2.00
(See also page 25, section 3.5)
Display
P5 Dither amplitude
0.00...3.03 V
of 0...30%; a setpoint of 3 V
corresponds to 30 %
see also page 25, section 3.6)
P6 Dither frequency
variable in steps from 0 to 647 Hz
(steps: 0, 16, 40, 60, 80, 110, 130,
160, 220, 327, 647 in Hz)
(See also page 25, section 3.6)
P7 Step function for solenoid A
0.00...max. *
(See also page 26, section 3.9)
P8 Step function for solenoid B
0.00...max. *
(See also page 26, section 3.9)
* Max. depending on solenoid type
0.8 A; 2.7 A or 3.5 A
Display
P9, P10
Initial current for solenoid A
and B, values in in mA
0.8A solenoid -205...+183
2.7A solenoid -704...+630
3.5A solenoid -917...+821
Display
P11
Command signal
not inverted 1
inverted -1
Display
P12
Actual value
not inverted 1
inverted -1
P13 With E2 = 1, 2, 4:
0...255
P-portion (K
P,1
)
for control deviation threshold (P15)
With E2 = 3:
0...255
P-portion (K
PBP
) bypass-loop
P14 T-portion of PT
1
-element
0...255
(affects P16)
P15 With E2 = 1, 2, 4:
0.00...9.99V
Threshold for switch over to K
P,2
With E2 = 3: not active
Also available with the closed loop version:
The display’s resolution is lower than
the input resolution. This is why only
every 2nd ... 4th key actuation leads to
a change in the display.
Initial currents are necessary with di-
rectly operated directional valves NG6
and NG10 with spool position transduc-
ers to ensure correct measurement of
displacement.
The drive should be switched off whilst
adjusting parameters.
On pages 35 and 36 all P- and E-para-
meters are listed with their default val-
ues. Display of sign, see page 34.
No solenoid current output is possible
with P3, P4 = 0.00.

Related product manuals