EasyManua.ls Logo

Pego PLUS300 EXPERT U THR - Page 24

Pego PLUS300 EXPERT U THR
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PLUS300 EXPERT U THR
Pag. 24
USE AND MAINTENANCE MANUAL
Rev. 01-18
Parameter C1 introduces a delay between a switch-off and the subsequent re-activation of
the cold. Hot can be deactivated with parameter EnH (EnH=0 disables the hot relay in all
conditions).
HUMIDITY/DEHUMIDIFICATION: PRESERVATION OF AMBIENT HUMIDITY
The humidity and the dehumidification call is managed in neutral area depending on the
set humidity setpoint ( key 4) and to the humidity differentials (parameters dUU and
dUd). Dehumidification is activated upon exceeding of set + dUd and remains active until
set is achieved (with dUn=0). Humidification is activated below set - dUU and remains
active until set is achieved (with dUn=0).
It is possible to set a "dead area" with parameters dUn that deactivates humidification and
dehumidification when humidity is between SET-dUn and SET+dUn.
The humidity management can be excluded with parameter Hr.
Dehumidification only can be excluded with parameter End.
Humidification only can be excluded with parameter EnU.
There are three dehumidification methods (parameter dEU):
1. Dehumidifies with the cold (the cold is called to dehumidify, the hot is added only to
maintain ambient temperature)
2. Dehumidifies with the hot (the hot is called to dehumidify, the cold is added only to
maintain ambient temperature)
5.15
CHAP. 5 - Parameters programming

Related product manuals