- 15 -
REMOTE ACCESS CONTROL
AIR CONDITIONER UNIT COMMUNICATION FEATURES (OPTIONAL)
An optional communication board offers capabilities that include SNMP, EtherNet/IP, Modbus TCP and Profinet
protocols through Ethernet and Modbus RTU protocol via USB. Pentair has a PC Interface Tool available for
download that can utilize either mode to communicate with the air conditioner unit.
USB COMMUNICATION
This communication mode allows direct connection of a PC to the air conditioner unit. The protocol
supported is Modbus RTU. Use the Pentair AC monitor to communicate with the air conditioner unit. A
MINI-b USB connection is included with this option.
ETHERNET COMMUNICATION
This communication mode allows remote connection to the air conditioner unit using SNMP, EtherNet/IP
and Modbus/TCP, and Profinet protocols. Customers using their own software can download a MIB file for
SNMP, EDS file or EtherNet_IP Object file for EtherNet/IP, Coil Register file for Modbus TCP and GSDML
file for Profinet.
Note: ACU has a default IP Address of 192.168.1.2
Both Ethernet and USB communication modes allow the ability to:
Read ACU inlet and outlet air temperatures
Read and change Cooling Set-point and Cooling Differential
Read and change High and Low Temperature Alarm Settings
Read and change Gateway IP Address, Device IP Address, Subnet Mask, Trap IP Address and SNMP Community
Read and change Unit Identification
Read and change the type of IP addressing (static or dynamic)
Read current Alarm Status
Read MAC address
SOFTWARE AND CONFIGURATION FILE DOWNLOADS
The Pentair AC monitor, MIB file, EDS file, EtherNet_IP Object file, Coil Register file and GSDML file for
Profinet can be downloaded from www.pentairprotect.com/en/na/Product-EnclosureCoolingHeating.
REMOTE ACCESS CONTROL PINOUT
FUNCTION NAME PIN #
U1 OUTPUTS
COOL No1 1
C1/2 2
C1/2 3
ALARM RELAY OUTPUT No5 12
C5 6
U2 INPUTS
ENCLOSURE DOOR SWITCH ID1 8
MALFUNCTION NC SWITCH ID2 1
NA ID3 (na) 9
NA ID4 (na) 2
DIGITAL INPUT GROUND ID GND 3
T1, EVAP IN THERMISTOR B1 13
T2, EVAP OUT THERMISTOR B2 12
T1, T2 GND GND 6
NA B3 11
CONTROLLER POWER G 7
CONTROLLER POWER G0 14
U3 DATA
POWER 1
GROUND 2
DIRECTION 3
DATA 4