S06 UNIT CHARACTERISTICS
UNIT 300W 115V 300W 230V 500W 115V 500W 230V
CATALOG NUMBER
Indoor Model without Communications Board (°C Controller) S060316G031 S060326G031 S060516G031 S060526G031
Indoor Model with Communications Board (°C Controller) S060316G041 S060326G041 S060516G041 S060526G041
Indoor Model without Communications Board (°F Controller) S060316G050 S060326G050 S060516G050 S060526G050
Indoor Model with Communications Board (°F Controller) S060316G060 S060326G060 S060516G060 S060526G060
COOLING PERFORMANCE
Total L35 L35, 50Hz, according to DIN EN 14511 (Watt) 370 370 550 550
Cooling performance L35 L35 (Watt) 50/60Hz 370 / 420 370 / 420 550 / 640 550 / 640
Cooling performance L35 L50 (Watt) 50/60Hz 190 / 230 190 / 230 320 / 380 320 / 380
Refrigerant R134a R134a R134a R134a
Refrigerant Charge (g) 133 128 162 162
Max. allowable operating pressure (p. max.) bar 28 28 28 28
Operating Temperature Range (Min/Max °C)
10 / 52 (50Hz)
10 / 55 (60Hz)
10 / 55 10 / 55 10 / 55
Operating Temperature Range (Min/Max °F)
50 / 126 (50Hz)
50 / 131 (60Hz)
50 / 131 50 / 131 50 / 131
Setting Temperature Range (Min. / Max. °C Controller ) 20 / 55 20 / 55 20 / 55 20 / 55
Setting Temperature Range (Min. / Max. °F Controller) 72 / 120 72 / 120 72 / 120 72 / 120
Airflow at 0 Static Pressure:
Internal loop (m³/h) 109 / 124 109 / 124 197 / 233 197 / 233
External loop (m³/h) 129 / 156 129 / 156 189 / 219 189 / 219
Duty Cycle 100% 100% 100% 100%
ELECTRICAL DATA
Rated Voltage (Volt) 100 / 115 230 115 230
Phase 1~ 1~ 1~ 1~
Frequency (Hz) 50/60 50/60 50/60 50/60
Operating Range +/- 10% +/- 10% +/- 10% +/- 10%
Max power Consumption 50/60Hz L35 L35 (Watt) 270 / 300 300 / 320 450 / 470 450 / 480
Max power Consumption 50/60Hz L35 L50 (Watt) 280 / 320 330 / 350 490 / 540 510 / 540
Max. Nominal Current (Amps) 4.0 / 3.8 1.8 / 1.7 6.5 / 6.1 2.6 / 2.9
Starting Current (Amps) 13 / 13 6.0 / 6.0 21 / 20 9.0 / 6.0
Pre-fuse T (Amps) 15 15 15 15
Agency Approvals UL listed, cUL listed, GOST, CE
Power Input Description Terminal Block
PERFORMANCE FACTOR (EER), 50Hz, DIN EN 14511
Cooling Performance L35 / L35 1.37 / 1.40 1.23 / 1.31 1.22 / 1.36 1.24 / 1.35
Cooling Performance L35 / L50 0.68 / 0.70 0.58 / 0.65 0.64 / 0.70 0.62 / 0.70
ENCLOSURE PROTECTION
IP Code (External loop / Internal loop) IP34 / IP54 IP34 / IP54 IP34 / IP54 IP34 / IP54
CONTROLLER
Description Smart controller with display
Controller Location Ambient side
Factory Default Setpoint (°C Controller) 35 35 35 35
Factory Default Setpoint (°F Controller) 80 80 80 80
SOUND LEVEL
At 1 M (dBA) 66 66 70 70
UNIT CONSTRUCTION
Material Steel Steel
Finish RAL 7035 RAL 7035
UNIT DIMENSIONS
Height (mm)
550 550 550 550
Width (mm)
280 280 280 280
Depth (mm)
140 140 206 206
Weight (kg)
13 13 15 15