PMI360DV-F130-IU-V15
Inductive angle positioning
system
Manual

Questions and Answers

  • J
    joseph50Aug 18, 2025
    Why "Power/Error" LED does not light up on Pepperl+Fuchs PMI360DV-F130-IU-V15?
    • F
      Felicia WellsAug 18, 2025
      If the "Power/Error" LED of your Pepperl+Fuchs Measuring Instruments does not light up, there could be several reasons: * The power supply might be off. Check if there's a reason for this (like maintenance) and switch it on if appropriate. * The cordset might not be properly connected. Ensure it is connected to the sensor and the union nut is tightened. * There could be a wiring fault in the splitter or control cabinet. Carefully inspect the wiring and repair any faults. * The supply cable to the sensor might be damaged. If so, replace the cable.
  • C
    christineelliottAug 20, 2025
    What to do if "Power/Error" LED lights up red permanently on Pepperl+Fuchs PMI360DV-F130-IU-V15?
    • J
      John ParkerAug 20, 2025
      If the "Power/Error" LED of your Pepperl+Fuchs Measuring Instruments lights up red permanently or intermittently, it could be due to the absence of an actuator in the sensor's detection area, or unreliable actuator detection. To resolve this, verify that the actuator is mounted correctly, or install an actuator with appropriate dimensions at the correct distance from the sensor.
  • R
    Robert RogersAug 22, 2025
    Why analog current output yields a value of approx. 3.6 mA on Pepperl+Fuchs Measuring Instruments?
    • W
      Wanda HoldenAug 22, 2025
      If the analog current output of your Pepperl+Fuchs Measuring Instruments yields a value of approximately 3.6 mA, it could be due to: * No actuator in the detection area of the sensor or unreliable detection of the actuator. Check that the actuator used is mounted correctly or install an actuator with appropriate dimensions at the correct distance from the sensor. * Actuator outside of parameterized measurement range. Check that the position of the parameterized measurement range is correct.
  • B
    Brett BondAug 26, 2025
    What to do if after programming, the function of the output remains unchanged in Pepperl+Fuchs PMI360DV-F130-IU-V15?
    • D
      Dean StewartAug 26, 2025
      If, after programming your Pepperl+Fuchs Measuring Instruments, the output function remains unchanged, it may be because the programming process wasn't completed within the 1-minute timeframe, or the wrong button was pressed. To fix this, complete the programming process by pressing the correct button for the output a third time within the time frame.
  • C
    Catherine HallAug 27, 2025
    Why analog output does not reach the maximum value on Pepperl+Fuchs PMI360DV-F130-IU-V15 Measuring Instruments?
    • L
      lisa64Aug 28, 2025
      If the analog output of your Pepperl+Fuchs Measuring Instruments does not reach the maximum value, the sensor operating voltage may be too low, or the load impedance may be out of specification. Check the operating voltage of the sensor and ensure the load impedance is within the specified limits.
  • P
    Paul ValdezAug 30, 2025
    What does it mean when a yellow LED flashes and the "Power/Error" LED flashes red at the same time on Pepperl+Fuchs Measuring Instruments?
    • S
      Sean ClarkeAug 30, 2025
      If a yellow LED flashes and the "Power/Error" LED flashes red simultaneously on your Pepperl+Fuchs Measuring Instruments, the button assigned to the flashing yellow LED is likely stuck. Remove any dirt or foreign objects that are causing the key to stick.
  • L
    Laura JacksonSep 1, 2025
    Why output signal unstable or unreliable on Pepperl+Fuchs PMI360DV-F130-IU-V15?
    • S
      snyderlindsaySep 1, 2025
      If the output signal of your Pepperl+Fuchs Measuring Instruments is unstable or unreliable, the actuator may be rotating too quickly. Ensure that the speed of the actuator is no more than 100 rotations per minute.
  • R
    Richard JohnsonSep 4, 2025
    What to do if output signal outside the value range specified at the analog output on Pepperl+Fuchs PMI360DV-F130-IU-V15?
    • F
      frank04Sep 4, 2025
      If the output signal of your Pepperl+Fuchs Measuring Instruments is outside the specified value range at the analog output, it could be because the load was connected only after the sensor was switched on. To resolve this, disconnect the sensor from the supply voltage and then switch it back on with the load connected.
  • J
    Jesse SavageSep 6, 2025
    What to do if LED stops flashing during the programming process of Pepperl+Fuchs PMI360DV-F130-IU-V15?
    • D
      Dennis VargasSep 6, 2025
      If the LED stops flashing during the programming process of your Pepperl+Fuchs Measuring Instruments, it's likely due to a timeout while programming the output, which occurs 1 minute after the last input. To continue, move the sensor again in programming mode.
  • K
    Kimberly WrightSep 9, 2025
    What to do if sensor cannot be moved in programming mode and "Power/Error" LED lights up red on Pepperl+Fuchs Measuring Instruments?
    • R
      Robert CallahanSep 9, 2025
      If the sensor of your Pepperl+Fuchs Measuring Instruments cannot be moved in programming mode and the "Power/Error" LED lights up red, it indicates that no actuator is available or the actuator is mounted too far from the sensor's surface. Mount the actuator according to the specified guidelines.

Pepperl+Fuchs PMI360DV-F130-IU-V15 Specifications

General IconGeneral
BrandPepperl+Fuchs
ModelPMI360DV-F130-IU-V15
CategoryMeasuring Instruments
LanguageEnglish