5. Assembly,setupandinstallation
5.1 Hazardwarnings
Ifanyimpuritiesgetintothesprinkler,itispossiblethatthesprinklercould
bedestroyedandthatfitterscouldbeinjured.Thereforeflushouttheline
thoroughlybeforeconnectingthewatersupply.
Anyunexpectedemergenceofajetofwatercanleadtoseriousinjury.
Thereforemakesurethattheinstallationhasbeenfullycompletedbefore
turningonthewatersupply.
5.2 Installationinstructions
Thethreadconnectiononthepopupsprinkleris2"FT.
Forthethreadsealusehempandsealingcompound,e.g.FermitSpezialor
teflontape.
Thepopupsprinklershouldbefittedinaccordancewiththe'PerrotVP3pop
upsprinklerinstallationdiagram'(seenextpage).Inordertoavoidanyload
pressureonthemainline,youshoulddefinitelyuseaflexibleconnection.
Providingadrainagepitdirectlyconnectedtothedrainage,asshowninthe
installationdiagram,isverymuchrecommended.
Forscrewingintheconnectionjointthehousingorhousingedgeofthepopup
sprinklercanbefirmlyheldorclamped.